![ComAp ID-Lite Скачать руководство пользователя страница 155](http://html1.mh-extra.com/html/comap/id-lite/id-lite_global-manual_2638907155.webp)
ID-FLX Lite & Telecom Global Guide
155
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
0 .. 180 [s]
Default value
10
-
Step
1
Comm object
9267
Related applications
Description
Delay for Wrn/Sd AIN8 alarm.
Note:
Analog input 8 is configurable with basic two levels protection and it is voltage type of input with
range 0-10 V.
AIN8 Del
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
0 .. 10000 [U15]
Default value
20
-
Step
1
Comm object
9268
Related applications
Description
Warning limit level for AIN9.
AIN9 Level 1
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
0 .. 10000 [U15]
Default value
10
-
Step
1
Comm object
9269
Related applications
Description
Shutdown limit level for AIN9.
AIN9 Level 2