![ComAp ID-Lite Скачать руководство пользователя страница 154](http://html1.mh-extra.com/html/comap/id-lite/id-lite_global-manual_2638907154.webp)
ID-FLX Lite & Telecom Global Guide
154
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
0 .. 3600 [s]
Default value
10
-
Step
1
Comm object
13349
Related applications
Description
High level protection delay for Wrn and Sd of AIN7.
Note:
In the alarm list is only displayed Wrn/Sd alarm on the appropriate analog input. There is not
resolution Low/High alarm.
Note:
Analog input 7 is fully configurable and it is voltage type of input with range 0-10 V.
AIN7 HighDel
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
0 .. 10000 [U14]
Default value
20
-
Step
1
Comm object
9265
Related applications
Description
Warning limit level for AIN8.
AIN8 Level 1
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
0 .. 10000 [U14]
Default value
20
-
Step
1
Comm object
9266
Related applications
Description
Shutdown limit level for AIN8.
AIN8 Level 2
Содержание ID-Lite
Страница 16: ...ID FLX Lite Telecom Global Guide 16 4 3 Terminal diagram and dimension...
Страница 18: ...ID FLX Lite Telecom Global Guide 18 Example Default analog output curves...
Страница 19: ...ID FLX Lite Telecom Global Guide 19 Example Wiring for Dacon gauges and IL NT AOUT8...
Страница 40: ...ID FLX Lite Telecom Global Guide 40 When you finish with adjusting the values click OK and Write to controller...
Страница 41: ...ID FLX Lite Telecom Global Guide 41 5 2 Binary inputs and outputs...
Страница 54: ...ID FLX Lite Telecom Global Guide 54 5 14 Display screens and pages structure...