![ComAp ID-Lite Скачать руководство пользователя страница 141](http://html1.mh-extra.com/html/comap/id-lite/id-lite_global-manual_2638907141.webp)
ID-FLX Lite & Telecom Global Guide
141
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
-100 .. 10000 [°C]
Default value
90
-
Step
1
Comm object
8376
Related applications
Description
Shutdown limit level for ANALOG INPUT 2.
AIN2 Level 2
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
0 .. 180 [s]
Default value
5
-
Step
1
Comm object
8371
Related applications
Description
Delay for ANALOG INPUT 2 alarm.
Note:
Analog input 2 is usually determined to Engine Temperature measurement and it is resistive type
of input with range 0-2500 Ω.
AIN2 Del
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
-100 .. +10000 [%]
Default value
20
-
Step
1
Comm object
8381
Related applications
Description
Warning limit level for ANALOG INPUT 3.
AIN3 Level 1
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
-100 .. 10000 [%]
Default value
10
-
Step
10
Comm object
8382
Related applications
Description
Shutdown limit level for ANALOG INPUT 3.
AIN3 Level 2
Содержание ID-Lite
Страница 16: ...ID FLX Lite Telecom Global Guide 16 4 3 Terminal diagram and dimension...
Страница 18: ...ID FLX Lite Telecom Global Guide 18 Example Default analog output curves...
Страница 19: ...ID FLX Lite Telecom Global Guide 19 Example Wiring for Dacon gauges and IL NT AOUT8...
Страница 40: ...ID FLX Lite Telecom Global Guide 40 When you finish with adjusting the values click OK and Write to controller...
Страница 41: ...ID FLX Lite Telecom Global Guide 41 5 2 Binary inputs and outputs...
Страница 54: ...ID FLX Lite Telecom Global Guide 54 5 14 Display screens and pages structure...