ID-FLX Lite & Telecom Global Guide
102
Setpoint group
Basic settings
Related FW
2.5.0
Range [units]
[ECU, INTERNAL, AUTO]
Default value
-
Step
-
Comm object
13345
Related applications
Description
This setpoint is used for adjustment of RunHours source of the engine.
ECU
RunHours are all the time read from ECU.
INTERNAL
RunHours are counted from the inner counter of the controller.
AUTO
If is coming from ECU rational value higher than 0, then the RunHours are taken from
ECU, in second case are displayed internal hours from controller. Default state.
IMPORTANT: Some types of ECUs reset RunHours counter to 0, if the supply was
disconnected.
RunHoursSource
Setpoint group
Basic settings
Related FW
2.5.0
Range [units]
[SHOW TIMERS, SHOW AIN]
Default value
-
Step
-
Comm object
13346
Related applications
Description
Change the display of the main Measurment screen.
SHOW TIMERS Standard display with timers on the left side of the screen. Default state.
SHOW AIN
Instead of timers are on the left side of the screen displayed values of analog inputs AIN6
and AIN7.
Main Screen
Содержание ID-Lite
Страница 16: ...ID FLX Lite Telecom Global Guide 16 4 3 Terminal diagram and dimension...
Страница 18: ...ID FLX Lite Telecom Global Guide 18 Example Default analog output curves...
Страница 19: ...ID FLX Lite Telecom Global Guide 19 Example Wiring for Dacon gauges and IL NT AOUT8...
Страница 40: ...ID FLX Lite Telecom Global Guide 40 When you finish with adjusting the values click OK and Write to controller...
Страница 41: ...ID FLX Lite Telecom Global Guide 41 5 2 Binary inputs and outputs...
Страница 54: ...ID FLX Lite Telecom Global Guide 54 5 14 Display screens and pages structure...