ECON-4 1.4.0 Global Guide
73
Setpoint group
Analog sensors
Related FW
1.4.0
configured ECON-4 extension
module
Range [units]
0 – 100 %
Default value
0 %
Force value
NO
Step
1 %
Comm object
11643
Related applications
ALL
Setpoint visibility
WinScope only
Description
Analogue output low limit signal definition.
AOUT 0
Setpoint group
Analog sensors
Related FW
1.4.0
configured ECON-4 extension
module
Range [units]
0 – 100 %
Default value
100 %
Force value
NO
Step
1 %
Comm object
11645
Related applications
ALL
Setpoint visibility
WinScope only
Description
Analogue output high limit signal definition.
AOUT 100
Setpoint group
Analog sensors
Related FW
1.4.0
configured ECON-4 extension
module
Range [units]
0,40 – Fdb1 100 pos.V
Default value
01.76 V
Force value
NO
Step
0.01 V
Comm object
11662
Related applications
ALL
Setpoint visibility
WinScope only
Description
Feedback fully closed position voltage. Connect the position feedback to the ECON-4 terminals. Keep the
actuator lever in fully closed position and measure a dc voltage between the terminals S2.1 and S2.3. This
voltage put as this setpoint value.
FBD 0 pos