ECON-4 1.4.0 Global Guide
68
Setpoint group
Main PID
Related FW
1.4.0
configured ECON-4
ADV extension module
Range [units]
0 – 100.0 %
Default value
0%
Force value
NO
Step
1 %
Comm object
14406
Related applications
ALL
Setpoint visibility
WinScope only
Description
Amount of derivation when Load decreases
LAder-
Setpoint group
Main PID
Related FW
1.4.0
configured ECON-4
ADV extension module
Range [units]
1.01 – 10.00 %
Default value
10
Force value
NO
Step
0.01 %
Comm object
14404
Related applications
ALL
Setpoint visibility
WinScope only
Description
Derivation curve definition – drop from + value. Initial value is divided by this number repeatedly once per
0.1s. So higher value means faster drop to zero.
LAder+recover
Setpoint group
Main PID
Related FW
1.4.0
configured ECON-4
ADV extension module
Range [units]
1.01 – 10.00 %
Default value
10
Force value
NO
Step
0.01 %
Comm object
14407
Related applications
ALL
Setpoint visibility
WinScope only
Description
Derivation curve definition – drop from - value. Initial value is divided by this number repeatedly once per
0.1s. So higher value means faster drop to zero.
LAder-recover