COMAC CAL FLOW 32 Скачать руководство пользователя страница 4

FLOW 32 manual 

 

 

 

   Page 4 (total 18) 

 

  COMAC CAL s.r.o. 

Installation in pipeline 

 
 

Important information for selection of location 

 

 
Outdoor conditions

 

It  is  necessary  to  ensure  that  the  flow  sensor  is  not  exposed  to  weather  effects  and  that  the 
measured medium cannot freeze in the flow sensor as it would damage the measuring tube.  
In  case  of  outdoor  location  of  the  flow  meter,  the  manufacturer  recommends  using  a 
protective box or a roof to avoid direct solar exposure so that the meter cannot get overheated. 
 

 

Sources of disturbances 

The following items rank among the most frequent sources of disturbances to the steady flow 
of liquid: 

 

Abrupt changes in pipe cross-section if not performed as  a cone with an angle of 

 

 7° 

(where 

 is the angle made by bevelled walls of the pipe reduction). 

 

Incorrectly  centred  sealing,  low  ID  sealing  or  sealing  made  of  soft  elastic  materials 
which are pushed out into the interior pipe cross-section after flanges are tightened. 

 

Anything  interfering  in  the  flow  of  liquid,  for  example  thermowells,  branch  pipes,  T-
pieces,  bends,  elbows,  slide  valves,  cocks,  flap  valves,  shut-off  valves,  control  valves, 
butterfly valves and check valves. Pipe outlets from tanks, heat exchangers and filters. 

 

No  intensive  magnetic  fields  in  the  proximity  of  the  induction  flow  sensor  (detector) 
must be present. 

No sources of disturbances

 affecting the steady flow must be present in the straight pipeline 

sections.  They must be located in  the piping after the flow sensor or at  the farthest  distance 
before it. Sources of disturbances may substantially reduce the measuring range and accuracy 
of the flow meters. 

 
Vibration

 

We  recommend  supporting  the  connecting  pipes  on  both  sides  of  the  meter  for  partial 
elimination of vibrations. Levels and range of vibrations must be under 2.2 in the frequency 
range of 20 ÷ 50 Hz according to IEC 068-2-34.  
 

Actual location

 

The flow sensor (detector) must not be at the top position of the pipe which may be airlocked, 
or  in  declining  or  even  in  horizontal  pipelines  with  open  ends  in  which  air  may  penetrate. 
Impurities  may  accumulate  during  long-term  measurement  of  very  low  flow  rates  Q  <  0.1 
m/sec. There must be a sufficient pressure in the place of flow sensor installation so that the 
expulsion  of  gas  or  vapour  bubbles  from  the  liquid  is  avoided.  Little  bubbles  that  always 
occur  in  liquids  may  accumulate  at  any  of  the  electrodes  and  this  may  result  in  incorrect 
operation of the meter.  Gas  bubbles are expelled also  at  an abrupt pressure drop. Therefore, 
butterfly valves and similar elements should be located 

after the flow sensor

. For the same 

reason, the flow sensor should not be placed at the suction side of the pump. To prevent the 
bubbles from accumulation at a low flow in the flow sensor, it is suitable, e.g. that the pipe is 
slightly ascending or that the flow sensor is located in the vertical section of the pipeline. 
 
 

Содержание FLOW 32

Страница 1: ...FLOW 32 Ver 4 0 Installation and technical conditions Date of issue 18 06 2019...

Страница 2: ...line 6 Installation check 8 Wiring system 8 Meter wiring 8 Impulse output OUT1 OUT2 9 Status output OUT3 10 Current output 10 Feasible output configurations 10 Wiring check 11 Putting into operation 1...

Страница 3: ...tion design The electronic evaluation unit is incorporated right in the flow meter section in order to form its integral part the respective flow rate sensor grounding electrodes are formed by threade...

Страница 4: ...affecting the steady flow must be present in the straight pipeline sections They must be located in the piping after the flow sensor or at the farthest distance before it Sources of disturbances may s...

Страница 5: ...take pipe Horizontally laid pipeline Long pipeline Free inlet or outlet Pumps The flow of liquid flow in the flow sensor should be steady and free of whirling For this reason straight sections of pipe...

Страница 6: ...the user himself Actual installation in pipeline In case of any intervention in the measuring circuit it is necessary to consider the piping system as being filled up with medium regardless of the sta...

Страница 7: ...earth point of the meter with the electrical potential of the earthd so that proper earthing is reached and the meter can operate reliably Electrodes The purity of the electrodes may have an influence...

Страница 8: ...electrical equipment When the following operations are performed unprofessionally the claim on warranty for the resulting errors becomes extinct Prior to any manipulation with the meter switch off th...

Страница 9: ...of volumetric impulses and for metrological verification of the flow meter Conversion constant and pulse width are set by the manufacturer during production OUT2 can be configured by the manufacturer...

Страница 10: ...e current value is directly proportional to that of the flow in the sample The flow limits of the current output are arbitrarily adjustable by the manufacturer during production float data type by mea...

Страница 11: ...he supply voltage on the control PCB and stabilization of parameters of the meter takes place afterwards approx 5 sec After that period of time the meter starts measuring Meter status It is continuous...

Страница 12: ...ated on the flow meter Safety rules for operator Any interventions in the inductive flow sensor and evaluation unit itself are illegal on the part of operator and they may lead to direct scalding by m...

Страница 13: ...DM and Silicone seals PVDF Measuring range Qmin Qmax unidirectional bidirectional for 0 2 12 m s 1 60 Accuracy 1 for 1 10 m s 2 for 0 2 1 m s Repeatability up to 0 4 for 0 1 10 m sec Min medium conduc...

Страница 14: ...ow ranges for individual DN sizes Diameter nominal mm Qmin m3 h Qmax m3 h DN 4 0 02 0 5 DN 6 0 03 1 DN 8 0 04 2 DN 10 0 06 3 DN 15 0 2 7 DN 20 0 25 10 Factory settings Impulse constants and current lo...

Страница 15: ...iameter nominal mm Threaded connection L1 L2 L3 W H1 H2 H3 K Compact flow meter weight kg 4 161 97 16 5 49 80 70 32 17 1 2 6 161 97 16 5 49 80 70 32 17 1 2 8 161 97 16 5 49 80 70 32 17 1 2 10 161 97 1...

Страница 16: ...rification of the flow meter functionality and connection to a higher level system after 3 minutes the flow meter goes back automatically to measurement mode Factory reset restoring the meter to facto...

Страница 17: ...extinct Before starting any work on the meter power supply must always be turned off Failures and their symptoms during measurement Unstable indication and outputs may occur upon high proportion of so...

Страница 18: ...is used in agreement with this manual the occurrence of faults is very rare Should they ever occur contact our service department If you return the meter to the manufacturing plant adhere to the cond...

Отзывы: