Coleman PCG4A36 Скачать руководство пользователя страница 1

TECHNICAL GUIDE

SINGLE PACKAGE 
AIR CONDITIONER / GAS HEAT
14 SEER – R-410A – 3 PHASE
3 THRU 5 NOMINAL TONS - 208/230V
50 THRU 125 MBH HEAT INPUT

MODELS: PCG4*36 THRU 60

Due to continuous product improvement, specifications 
are subject to change without notice.

Visit us on the web at 

www.upgnet.com and www.colemanac.com

Additional rating information can be found at:

www.ahridirectory.org

WARRANTY SUMMARY*

Standard 1-Year limited parts warranty.
Standard 5-Years limited compressor warranty.
Lifetime gas heat exchanger warranty with registration.

See limited warranty certificate in User’s Information Manual for details.

®

 

5564041-CTG-A-1018

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

DESCRIPTION

These packaged cooling/heating air conditioners are designed
for outdoor installation. Only utility and duct connections are
required at the point of installation.

FEATURES

Operating Efficiency 

- All PCG4 model gas units provide a

minimum AFUE of 81.0% in heating and 14.0 SEER, 11.0
EER rating for cooling operation. All models meet California
Low-Nox requirements of 40 ng/joule emission level for Air
Quality Management Districts.

On Site Flexibility -

 All model sizes use a compact design

cabinet in one of two footprints. This provides installer flexi-
bility for placing the proper capacity unit on curbs or pads
with the smallest footprint after the internal load has been
determined. Field convertible duct connections from side
shot to down shot allows the installer to have greater flexibil-
ity with less inventory.

Lower Installation Cost -

 Installation time and costs are

reduced by easy power and control wiring connections. The
small base dimension means less space is required on the
ground or roof. All units are completely wired, charged with
R-410A and tested prior to shipment. Test stations using a
state-of-the-art computerized process system are used to
insure product quality. Refrigerant charge and component
part numbers are verified via computers during assembly.
Vital run test statistics such as system pressure, motor cur-
rents, air velocity and temperature, unit vibration, and gas
system safeties are monitored and recorded by the system to
insure unit performance. Equal size side supply and return
duct connections allow easy connection of ducts to match
low crawl spaces without transition pieces.

Utility Connections Made Easy -

 Gas and electric utility

access provided through the bottom or the side of the unit.
Utility connections can be made quickly and with a minimum
amount of field labor. A field supplied and field installed elec-
trical disconnect switch must be installed.

Convertible Airflow Design -

 The bottom duct openings are

covered when they leave the factory, ready to be used for a
side supply/side return application. If a bottom supply/bottom
return application is desired, simply remove the two panels
from the bottom of the unit and place them in the side supply/
side return duct openings. No panel cutting is required and
no accessory panel is necessary. Convertible airflow design
allows maximum field flexibility and minimum inventory.

Condensate Pan -

 A corrosion-resistant, long-lasting, water-

tight pan is positioned below the evaporator coil to collect
and drain all condensate, preventing build-up of stagnant
condensate. The condensate pan conforms to ASHRAE 62-
89 standards (Ventilation for Acceptable Indoor Air Quality).

Condensate Drain -

 The 3/4 inch NPT female connection is

rigidly mounted to assure proper fit and leak tight seal.

Durable Finish -

 The cabinet is made of G90 galvanized

steel with a powder paint coating for appearance and protec-
tion. The pre-treated galvanized steel provides a better paint-
to-steel bond, which resists corrosion and rust creep. Pow-
der paint finish insure less fading when exposed to sunlight,
and provides superior corrosion resistance (1000 hour salt
spray tested).

Continued on next page.

Содержание PCG4A36

Страница 1: ...computerized process system are used to insure product quality Refrigerant charge and component part numbers are verified via computers during assembly Vital run test statistics such as system pressure motor cur rents air velocity and temperature unit vibration and gas system safeties are monitored and recorded by the system to insure unit performance Equal size side supply and return duct connect...

Страница 2: ...pressor compartment The controls are mounted to allow the separate access panel to be removed for trouble shooting and maintenance without affecting the normal system operating pressures All wiring internal to the unit is color number coded Protected Compressor The compressor is internally pro tected against high pressure and temperature This is accomplished by the simultaneous operation of high p...

Страница 3: ...g Capacity 24 Nominal Capacity etc 9 Revision Level A original release B second release Examples PCG4B421002X1A is a packaged A C with gas heat 14 SEER 3 1 2 ton large cabinet three stage heat 100 000 BTU gas heat 230 volt three phase low NOx model first generation first release COMPONENT LOCATION FAN MOTOR OUTDOOR FAN COIL GUARD PANEL OUTDOOR COIL Behind Panel CONTROL BOARD TRANSFORMER HIGH VOLTA...

Страница 4: ...rough 50 of outdoor air field supplied Closes on power loss includes hood and screen assembly Loss of Charge Switch S1 2LC00024 Kit provides Loss of Charge sensor and wiring to provide safe shutdown of compressor Rectangle to Round Horizontal Adapter S1 1AK0110 S1 1AK0111 Kit includes one supply and one return air rectangle to round duct adapter Adapters are preformed and designed to fit over curr...

Страница 5: ... Fan shall be direct drive design Fan wheel shall be double inlet type with forward curved blades dynamically balanced to operate smoothly throughout the entire range of operation Airflow design shall be constant air volume Bearings shall be sealed and permanently lubricated for longer life and no maintenance Fan assembly shall be a slide out design for easy removal and cleaning Indoor blower moto...

Страница 6: ...perating WT lbs 394 401 405 441 443 460 468 473 477 481 488 Compressors Type Scroll Scroll Scroll Scroll Outdoor Coil Data Face area Sq Ft 15 1 16 9 19 5 21 5 Rows 2 2 2 2 Fins per inch 22 22 22 22 Tube diameter 3 8 3 8 3 8 3 8 Circuitry Type Interlaced Interlaced Interlaced Interlaced Indoor Coil Data Face area Sq Ft 4 6 4 6 6 3 6 3 Rows 3 3 3 3 Fins per inch 16 16 16 16 Tube diameter 3 8 3 8 3 8...

Страница 7: ...6 8 24 4 20 2 20 9 16 2 28 5 26 9 22 1 23 1 17 4 K W 3 30 3 39 3 39 3 41 3 42 3 25 3 47 3 46 3 48 3 49 3 21 3 55 3 54 3 55 3 57 COOLING PERFORMANCE DATA 3 5 TON PACKAGED UNIT MODEL NO PCG4A42 CONDENSER ENTERING AIR TEMPERATURE ID CFM 1200 1400 1600 IDDB 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80 IDWB 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72 55 45 T C 43 7 46 9 46 8 51 8 57 3 46 5 48 6 48 5 5...

Страница 8: ...24 5 29 0 26 0 28 8 20 9 24 6 29 6 25 6 31 0 21 9 K W 5 30 5 29 5 30 5 33 5 35 5 37 5 36 5 36 5 39 5 41 5 44 5 42 5 42 5 45 5 47 COOLING PERFORMANCE DATA 5 TON PACKAGED UNIT MODEL NO PCG4B60 CONDENSER ENTERING AIR TEMPERATURE ID CFM 1600 1800 2000 IDDB 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80 IDWB 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72 55 45 T C 68 0 69 1 68 1 73 0 79 5 70 4 70 4 69 3 74...

Страница 9: ...ed space and recirculate Direction Distance in Direction Distance in Top3 3 Units must be installed outdoors Over hanging structure or shrubs should not obstruct condenser air discharge outlet 36 Power Entry Right Side 36 Side Opposite Ducts 36 Left Side 24 Duct Panel 0 Bottom4 4 Units may be installed on combustible floors made from class A B or C roof covering materials 1 92 7 23 1 1 92 7 23 1 1...

Страница 10: ...th AHRI Standard 270 Octave Band Centerline Frequency Hz 125 250 500 1000 2000 4000 8000 A36 74 58 5 61 8 65 4 66 5 60 7 54 8 49 8 A42 74 63 5 63 9 62 3 65 0 64 0 54 1 46 6 B48 74 63 5 63 9 62 3 65 0 64 0 54 1 46 6 B60 76 72 3 65 0 63 9 64 0 60 0 55 5 49 0 ELECTRICAL DATA Model Voltage Compressor OD Fan Motor Supply Blower Motor MCA1 Amps Max Fuse2 Breaker3 Size Amps RLA LRA MCC FLA FLA 36050 3607...

Страница 11: ... 406 401 28 15 135 115 103 74 36100 410 405 28 15 139 113 99 80 42075 446 441 28 15 145 112 99 85 42100 448 443 28 15 148 110 96 89 48065 465 460 28 15 189 116 93 117 48100 473 468 28 15 169 139 115 100 48125 478 473 28 15 164 145 124 95 60065 482 477 29 15 174 142 124 92 60100 486 481 28 15 177 140 117 102 60125 493 488 27 15 151 167 141 84 X CENTER OF GRAVITY FRONT OF UNIT Y D C B A A0295 001 TG...

Страница 12: ...55 1416 1376 1336 1294 1248 1156 Medium 3 1573 1523 1484 1445 1408 1367 1327 1279 1183 Medium High 4 1681 1640 1599 1557 1517 1478 1436 1393 1307 High 5 1935 1887 1834 1788 1743 1701 1651 1591 1471 48065 Low 1 1046 1009 980 946 915 878 844 779 649 Low Medium 2 1295 1250 1213 1172 1133 1087 1045 964 802 Medium 3 1620 1564 1517 1466 1418 1360 1308 1206 1002 Medium High 4 1798 1722 1669 1620 1572 152...

Страница 13: ... 1146 1103 1069 1030 977 912 781 Low Medium 2 1270 1225 1189 1140 1098 1046 1008 960 866 Medium 3 1317 1286 1245 1198 1151 1110 1064 1024 943 Medium High 4 1358 1317 1275 1238 1197 1148 1105 1057 961 High 5 1517 1475 1447 1400 1357 1318 1275 1232 1146 36100 Low 1 1340 1299 1264 1224 1182 1182 1097 1049 953 Low Medium 2 1409 1368 1334 1291 1253 1201 1173 1128 1038 Medium 3 1527 1492 1470 1419 1385 ...

Страница 14: ...65 Low 1 1026 999 989 950 907 907 886 862 816 Low Medium 2 1263 1230 1192 1165 1167 1101 1099 1071 1015 Medium 3 1987 1933 1861 1817 1820 1715 1725 1651 1504 Medium High 4 2114 2050 2047 1974 1899 1889 1920 1866 1758 High 5 2369 2308 2249 2183 2126 2088 2034 1990 1902 60100 Low 1 1655 1612 1596 1531 1461 1462 1429 1391 1316 Low Medium 2 1766 1720 1667 1629 1632 1539 1537 1498 1421 Medium 3 1987 19...

Страница 15: ... 06 0 04 0 06 1600 0 07 0 04 0 07 1700 0 07 0 04 0 08 1800 0 08 0 04 0 09 1900 0 09 0 05 0 10 2000 0 09 0 05 0 11 B48 4 0 1100 0 02 0 02 0 04 1200 0 03 0 02 0 04 1300 0 04 0 02 0 05 1400 0 05 0 03 0 05 1500 0 06 0 04 0 06 1600 0 07 0 04 0 07 1700 0 07 0 04 0 08 1800 0 08 0 04 0 09 1900 0 09 0 05 0 10 2000 0 09 0 05 0 11 B60 5 0 1100 0 02 0 02 0 04 1200 0 03 0 02 0 04 1300 0 04 0 02 0 05 1400 0 05 ...

Страница 16: ...ON REAR DUCT ROOF CURB INSTALLATION BOTTOM DUCT SLAB ON GROUND INSTALLATION A032 UNIT TYPICAL SLAB ON GROUND INSTALLATION A0325 001 SUPPLY AIR DUCT TO POWER SUPPLY RETURN AIR DUCT FIELD SUPPLIED DISCONNECT SWITCH CONTROL WIRING TO INDOOR THERMOSTAT TO GAS SUPPLY LINE MANUAL GAS SHUTOFF VAVLE CONDENSATE DRAIN ...

Страница 17: ...oducts 17 UNIT TYPICAL ROOF CURB INSTALLATION SUPPLY AIR DUCT TO POWER SUPPLY RETURN AIR DUCT FIELD SUPPLIED DISCONNECT SWITCH CONTROL WIRING TO INDOOR THERMOSTAT TO GAS SUPPLY LINE MANUAL GAS SHUTOFF VAVLE ROOF CURB ROOF CONDENSATE DRAIN A0326 001 ...

Страница 18: ... change without notice Published in U S A 5564041 CTG A 1018 Copyright 2018 by Johnson Controls Inc All rights reserved Supersedes 5006144 CTG F 1017 York International Corp 5005 York Drive Norman OK 73069 NOTES ...