
5493752-CTG-F-0420
Johnson Controls Ducted Systems
71
PERFORMANCE DATA - 4 TON
Multipliers for determining the performance with other indoor sections.
NOTE:
For dry bulb temperatures different than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
CONDENSER-ONLY DATA (OUTDOOR UNIT)
MODEL
SATURATED SUCTION
@ COMPRESSOR
Outdoor Ambient Temperature
55 °F
65 °F
75 °F
85 °F
95 °F
105 °F
115 °F
125 °F
T (°F)
P (PSIG)
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
AC19B4821S
(Stage 2)
35
107
46.8
2.68
44.4
2.94
42.1
3.22
39.7
3.55
37.3
3.91
34.8
4.34
32.1
4.83
29.2
5.38
40
118
51.4
2.70
48.8
2.95
46.3
3.23
43.8
3.54
41.2
3.91
38.4
4.34
35.5
4.83
32.4
5.38
45
130
55.8
2.74
53.5
2.96
50.9
3.23
48.1
3.54
45.3
3.90
42.3
4.33
39.2
4.83
35.8
5.37
50
142
60.8
2.79
58.6
2.97
55.7
3.23
52.8
3.54
49.7
3.89
46.5
4.32
43.1
4.82
39.5
5.36
55
156
67.0
2.77
64.0
2.99
60.9
3.24
57.7
3.55
54.4
3.90
51.0
4.32
47.3
4.81
43.4
5.35
AC19B4821S
(Stage 1)
35
107
32.2
1.81
30.2
2.05
28.2
2.32
26.1
2.63
23.6
2.97
20.9
3.37
17.7
3.81
14.1
4.30
40
118
35.6
1.76
33.5
2.00
31.4
2.27
29.2
2.58
26.6
2.92
23.7
3.32
20.4
3.76
16.6
4.25
45
130
39.3
1.72
37.1
1.96
34.9
2.22
32.5
2.53
29.8
2.87
26.8
3.26
23.3
3.71
19.3
4.19
50
142
43.2
1.67
40.9
1.91
38.6
2.18
36.1
2.47
33.2
2.81
30.1
3.21
26.4
3.65
22.3
4.14
55
156
47.3
1.63
44.8
1.87
42.5
2.13
39.9
2.42
36.9
2.75
33.6
3.14
29.8
3.59
25.5
4.07
Notes:
1. For Outdoor Unit (Condenser) performance only. Data does not include the effects of air handler power or heat.
2. Performance based on 15°F subcooling and 15°F superheat at the Outdoor Unit base valves.
a. Increase capacity by 1% for each 2°F increase in subcooling.
b. Decrease capacity by 1% for each 2°F decrease in subcooling.
3. Maximum recommended condensing temperature is 140°F.
COOLING PERFORMANCE DATA
OUTDOOR UNIT MODEL NO.
AC19B4821S
INDOOR COIL MODEL NO.
CF64DXA1
AIR TEMP.
ENTERING
OUTDOOR UNIT (°F)
ID CFM
1350
1600
1850
ID DB (°F)
80
80
75
80
80
80
80
75
80
80
80
80
75
80
80
ID WB (°F)
57
62
62
67
72
57
62
62
67
72
57
62
62
67
72
55
T.C.
44.6
48.8
48.8
52.6
54.7
46.8
50.0
50.0
53.3
55.3
48.9
51.1
51.2
54.0
56.0
S.C.
44.6
39.8
33.8
32.5
24.6
46.8
42.5
35.6
33.4
24.8
48.9
45.2
37.5
34.4
25.0
KW
2.42
2.44
2.44
2.47
2.48
2.52
2.54
2.54
2.56
2.57
2.63
2.64
2.64
2.66
2.66
65
T.C.
43.3
47.2
47.4
51.7
54.9
45.5
48.5
48.6
52.6
55.9
47.7
49.7
49.9
53.5
56.8
S.C.
43.3
39.4
33.4
32.6
25.1
45.5
42.4
35.5
34.1
25.8
47.7
45.4
37.6
35.7
26.5
KW
2.65
2.68
2.68
2.72
2.74
2.76
2.78
2.78
2.81
2.83
2.87
2.88
2.88
2.91
2.93
75
T.C.
42.0
45.7
46.1
50.8
55.1
44.2
47.0
47.3
51.9
56.4
46.5
48.3
48.5
53.0
57.7
S.C.
42.0
38.9
32.9
32.7
25.7
44.2
42.3
35.3
34.8
26.8
46.5
45.6
37.7
37.0
28.0
KW
2.89
2.92
2.92
2.96
3.00
3.00
3.02
3.02
3.06
3.10
3.11
3.12
3.12
3.16
3.19
85
T.C.
40.8
43.9
44.1
48.8
53.3
42.8
45.1
45.4
49.9
54.6
44.8
46.4
46.6
51.0
56.0
S.C.
40.8
38.3
32.1
32.0
25.0
42.8
41.7
34.6
34.3
26.2
44.8
45.1
37.2
36.6
27.4
KW
3.22
3.24
3.24
3.28
3.31
3.33
3.34
3.34
3.38
3.41
3.43
3.44
3.44
3.47
3.51
95
T.C.
39.6
42.1
42.2
46.9
51.5
41.4
43.3
43.5
48.0
52.9
43.2
44.5
44.7
49.1
54.2
S.C.
39.6
37.7
31.3
31.4
24.4
41.4
41.2
34.0
33.8
25.6
43.2
44.5
36.6
36.2
26.7
KW
3.54
3.56
3.56
3.59
3.63
3.65
3.66
3.66
3.69
3.72
3.75
3.76
3.75
3.79
3.82
105
T.C.
37.0
39.7
39.8
44.2
48.6
39.0
40.8
40.9
45.1
49.8
41.0
41.9
42.1
46.0
51.0
S.C.
37.0
36.4
30.3
30.1
23.4
39.0
39.3
32.9
32.7
24.7
41.0
41.9
35.5
35.2
25.9
KW
4.00
4.02
4.02
4.05
4.08
4.10
4.12
4.11
4.15
4.18
4.21
4.21
4.21
4.25
4.28
115
T.C.
34.5
37.4
37.4
41.6
45.7
36.7
38.4
38.4
42.3
46.8
38.8
39.4
39.5
43.0
47.9
S.C.
34.5
35.2
29.4
28.9
22.4
36.7
37.4
31.8
31.6
23.8
38.8
39.4
34.3
34.2
25.1
KW
4.44
4.46
4.46
4.49
4.53
4.55
4.56
4.56
4.60
4.63
4.66
4.65
4.65
4.70
4.72
125
T.C.
32.0
35.0
35.0
38.9
42.8
34.3
36.0
36.0
39.5
43.8
36.7
36.9
37.0
40.0
44.9
S.C.
32.0
33.9
28.4
27.7
21.5
34.3
35.6
30.8
30.4
22.9
36.7
36.9
33.2
33.2
24.2
KW
4.88
4.91
4.90
4.94
4.97
4.99
5.00
5.00
5.04
5.07
5.10
5.10
5.10
5.15
5.17
NOTE:
ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (O INDOOR).
Green shaded cells are ACCA (TVA) conditions.
Blue shaded cells are AHRI conditions.