Repair | 11
Operating instructions CMVpro 125-400 | Version 1-en
55 / 76
11
Repair
11.1
Safety instructions
These safety instructions warn against dangers that can arise when repairing
the fan.
WARNING
Risk of injury due to repair work on the fan
Injuries due to electrical, mechanical, and chemical hazards.
u
Only maintenance personnel authorized by the operator as well as service
personnel authorized by the distributor or manufacturer may carry out repair
work.
u
The safety instructions for maintenance work apply
_
51].
u
Allow the fan to cool off with the electric motor before beginning work.
u
An electrician is responsible for energization of the fan.
11.2
Fault table
Identify and rectify fan faults using this table, and enter them in the machine log-
book
_
74]. For further information, contact customer service (see
front page).
Fault
Possible cause
Fault discovery
Remedy
No function
No electrical power.
Check phase voltage.
Check electrical instal-
lation.
Volumetric flow
rate insuffi-
cient: operating
point according
to technical
data sheet can-
not be
reached.
Incorrect direction of
rotation of the impeller.
Visual inspection.
Swap phases
_
44].
Damper valve improp-
erly positioned.
Visual inspection.
Set damper valve to
proper position.
Pressure loss in duct-
work.
Measure flow rate and
pressure at the operat-
ing point.
Optimize ductwork lay-
out.
Inflow or outflow at the
fan causes high pres-
sure loss.
Adjust the speed for
the new conditions
within the limits of the
intended use.
Damper valve improp-
erly positioned in duct-
work.
Adjust the system.
Observe minimum dis-
tance between fan
connection and
damper valve or duct
bend (L > 3 x duct Ø).
Operating
speed cannot
be reached.
Faulty motor winding.
Winding measure-
ment.
Replace electric motor
_