Repair | 12
Operating instructions CMVpro 125-400 ATEX | Version 1-en
67 / 88
Fault
Possible cause
Fault discovery
Remedy
Impeller dips into con-
densate at bottom of
casing.
Type K: visual inspec-
tion.
Drain condensate
_
Type V: visual inspec-
tion.
Clean and replace
condensate drain/
siphon
_
-
Retrofit with casing
drain.
Loose/defective vibra-
tion absorbers or fas-
tening elements.
Visual inspection
Tightly screw/replace
vibration absorbers
_
and following.
Improper mounting.
Installation location re-
quirements
met
_
.
Fortify foundation
(baseplate). Resize
fastening elements
(anchors).
Overheating of
electric motor.
Bearing or winding
damage.
Auditory inspection,
current draw measure-
ment, winding mea-
surement.
Repair or replace elec-
tric motor
_
Impeller stiff or
stopped.
Visual inspection.
Remove deposits or
foreign objects
_
62].
Motor overload due to
improperly positioned
damper valve.
Measure flow rate and
pressure at the operat-
ing point.
Set damper valve to
proper position.
Motor overload due to
system changes.
Fan/electric motor no
longer meeting the op-
erating point.
Consult with point of
contact (see title
page).
FC does not reach re-
quired voltage.
Check FC.
Use a suitable FC.
Prohibited op-
erating condi-
tions.
Ductwork not leak
tight.
Check for leakage.
Seal up.
Loose hose clamps or
damaged sleeves.
Re-tighten hose
clamps or replace
sleeves
_
41].