Electrical installation | 8
Operating instructions CMVpro 125-400 ATEX | Version 1-en
53 / 88
To size the connection cable, consult the cable manufacturer's tables for cur-
rent-carrying capacity or request sizing information directly from the cable manu-
facturer.
When running the cable, observe the following essential principles:
• Avoid damaging the cable by pinching, cutting, pulling, etc. during installa-
tion.
• Run connection cables in the building securely with clamps or mounting
brackets, and protect them from damage with cable conduit.
• For protection against vibration, run the connection cable between the fan
and cable fasteners to the installation location such that it is flexible and
movable.
Making the cable connection
•
DANGER
Establish an electrically safe work condition before beginning
work.
• Connect the connection cable to the motor protection switch/fuses and the
isolation switch.
• Ensure correct connection of the phase conductors.
• Seal all cable entries such that they are splash-proof.
• Compare the existing mains voltage and mains frequency with the data on
the motor nameplate and determine the connection type of the electric mo-
tor (star or delta connection).
Y
W2
L1
L2
L3
U2
V2
W1
V1
U1
W2
L1
L2
L3
U2
V2
W1
V1
U1
Fig. 33:
Terminal assignment for delta and star connection
• Open terminal box on electric motor.
• If necessary, move the jumpers on the terminal board according to the ter-
minal assignment.
The terminal assignment is also located on the inside of the terminal box cover.
• Connect the phase conductors (L1, L2, L3) of the motor connection cable to
the terminal board in the correct order.