Digital fire detection control panel
LYON REMOTE PLUS
81
FIRE PROTECTION MANUFACTURER
C / Compositor Wagner, 8 –P.I. Can Jardí 08191 - RUBÍ (Barcelona) ESPAÑA.
Tlf.: +34 935 862 690 –
4.- Start-up.
4.1.- Prior verifications.
Prior to putting the
Lyon system
installation into operation, we must assure ourselves that the installation
is totally completed and we have all the data for its correct programming. For this it is necessary to verify
that the points shown below have been completed:
To have a 110~230V power source available dedicated to the fire protection system and that it is
live 24 hours a day, seven days a week. (see chapter 2.1)
To have a set of two 12V batteries with a capacity between 7 and 24Ah depending on the number
of loops and load connected to the control panel. (to see chapter 2.3.1)
To verify that all the elements are connected to the installation.
To verify that there are no installation elements left unconnected or with connection errors that
could cause faults when putting into operation or deterioration of the
Lyon system
elements.
Do not remove the covers until the installation is finished and clean.
To have a list with the total of connected elements of each type in each loop, see example in the
following table.
To have a list for each loop with the location, type and programming number of each element,
(sensor, button, relay module, technical signals module, addressable sirens, master module). This
programming number goes from 1 to 65533, see example in the following table:
Loop: 01
POINT
Prog. No.
Label
Type
Notes
1
12757
ROOM 101
A30XHA
2
12432
ROOM 102
A30XHA
3
4767
BUTTON P1
PUCAY
4
6982
CORRIDOR P1
KMAY
In this way with the lists made on-site, that are completed with the listings of relay activation and with the
relationship of alarm zones, it is possible to undertake the system programming working with an external
keyboard, on the control panel’s own keypad or much more easily using the
I-Link
program on a PC that
will later download to the control panel.
LOOP: 1
TYPE
AMOUNT
A30XHA/S
25
A30XTA
2
A30XHTCO
47
PUCAY
36
SIRAY
3
MDAXY
6
MSTAY
1
KMAY
3
TOTAL
123