Ku-Band BUC systems
Page 8 of 18
12-50176-EN Issue 2, December 2010
Cable installation
Where required, you
must
use standard shielded Codan cables for the power and control
cabling to ensure safety and EMI/EMC standards are met.
In installations where the cables are not supplied by Codan, all power and control cables
must
be assembled in accordance with drawings supplied by Codan.
General guidelines
Use the most direct route possible for the cable runs. Secure the cable runs with cable
ties or other suitable clamps.
You may install the indoor/outdoor interconnecting cables underground (in 75 mm PVC
pipe, for example), or supported by an overhead catenary wire. If the transmit and
receive IF coaxial cables are identical, mark the cables at each end before you install
them. Also, ensure that there is enough slack left to make antenna adjustments without
straining the cables.
Securing cables
Once connections have been made, it is important to secure cables so they do not hang
loosely or flap in the wind.
To ensure water drains off the cables and not onto the connections, create a loop in each
cable that hangs lower than the connectors.
CAUTION
Loose hanging cables tend to elongate over time, causing the conductors
to stretch and the performance of the cables to degrade.
CAUTION
The cables should be secured in such a way that water falling on the
cables does not run directly onto the connections.
Содержание 4908-MINIBUC
Страница 18: ...Ku Band BUC systems Page 18 of 18 12 50176 EN Issue 2 December 2010 This page has been left blank intentionally...
Страница 19: ...15 42072 001 sheet 1...
Страница 20: ...15 42072 001 sheet 2...
Страница 21: ...15 42098 001...
Страница 22: ...15 40128 001...
Страница 23: ...15 40147 001...
Страница 24: ...01 01192 CODAN...
Страница 25: ...01 01828...
Страница 26: ...01 01302...
Страница 27: ...01 01689...
Страница 28: ...01 01785...