CO2 Monitor Operating Instructions

 

 

Model: RAD-0102-6 Remote CO2 Storage Safety System 

 

1. Product Overview 

 
Thank you for selecting the RAD-0102-6 CO2 Storage Safety 
Alarm.  This  monitor  is  designed  to  detect  Carbon  Dioxide 
levels  in  the  ambient  air  to  protect  employees  and 
customers. CO2 monitors are required in most jurisdictions by 
code.    High  concentrations  of  CO2  in  confined  spaces  are 
dangerous,  and  may  lead  to  health  problems  ranging  from 
headaches  and  fatigue  to  asphyxiation  and  death.  This 
monitor has 3 audible and visual alarm levels with relays that 
are  triggered  at  5,000  ppm  TWA,  15,000  ppm,  and  30,000 
ppm and can control a ventilation fan or signal the fire panel 
to  send  an  alarm  to  the  fire  department  or  monitoring 
company.   These  standards  meet  IFC,  NFPA,  and  NBIC 
requirements for monitoring.  
 
RAD-0102-6 CO2 Monitor is cost-effective and includes these features: 

1.)  Multiple RDU’s can be connected for additional alarm points. 
2.)  Large digital LCD display clearly indicates the ambient CO2 concentration, 

relative humidity, and temperature. 

3.)  3 independent relay outputs can automatically control vent fan or be wired to the fire alarm 

panel. 

4.)  Audible and visual alarm indications. 
5.)  Automatic altitude compensation (can be turned on/off). 
6.)  4-20 mA output for offsite monitoring. 
7.)  100% clean look by burying all cables in the wall. 
8.)  Allows for field upgrades with strobe package at a later date. 

 

2. Package Content & Unit Layout   

 
The RAD-0102-6 package comprises the following parts: 
 

  SEU (Main Unit), 

  RDU (Remote Unit) 

  CAT 5 Communication Cable (1 piece) 

  Relay Cables (3 pieces) 

  Wall Plug Safety Strap (1 piece) 

  Mounting Brackets (2 pieces) 

  Screws (13 pieces), Wall Anchors (12 pieces), Cable Clips (10 pieces) 

  Power Supply (1 Piece), International Power Adaptors (3 pieces) 

  Warning Signs (6 pieces) 

  User Manual (1 piece). 

 
 

Содержание RAD-0102-6

Страница 1: ... monitoring RAD 0102 6 CO2 Monitor is cost effective and includes these features 1 Multiple RDU s can be connected for additional alarm points 2 Large digital LCD display clearly indicates the ambient CO2 concentration relative humidity and temperature 3 3 independent relay outputs can automatically control vent fan or be wired to the fire alarm panel 4 Audible and visual alarm indications 5 Autom...

Страница 2: ...N 4 20mA Out O Battery P DC Power Supply Q RDU Cable RJ45 R Relay 3 AL3 S Relay 2 AL2 T Relay 1 AL1 U Strobe Cable RJ45 V Panel Holder RDU Remote Display Unit A Power Green LED B AL1 Red 1 LED C AL2 Red 2 LED D AL3 Red 3 LED E Fault Yellow LED F LCD display G Mode Button H UP Button I Down Button J Enter Button K Buzzer L Strobe Cable RJ45 M Output Cable to RDU RJ45 N Input Cable from SEU RDU RJ45...

Страница 3: ...The AL2 Red 2 LED will flash The buzzer will sound see 9 3 AL3 3rd CO2 Alarm Level Relay 3 will be triggered when CO2 concentration exceeds the 3rd alarm level Preset at 30 000ppm The AL2 Red 2 LED AL3 Red3 LED and Fault LED will flash The buzzer will sound This status will be latched see 9 4 CALI Calibration To calibrate the CO2 sensor when the accuracy deviates from the actual CO2 concentration ...

Страница 4: ... Relay 2 will be triggered When the CO2 value drops below the AL2 CO2 level AL2 Red 2 LED will stop blinking the buzzer will stop and Relay 2 will be inactive If the CO2 concentration continues to rise and exceeds the AL3 CO2 level AL2 Red 2 LED and AL3 Red 3 LED will flash together The tempo of the flashing and buzzer will increase RAD 0102 6 will latch after this event When the CO2 value drops b...

Страница 5: ...nstructions Please carefully remove all items from the package and follow the Step by Step Installation Instructions 1 Choose a suitable location to install the SEU Fix the panel holder on the wall with the four screws Install the SEU 18 inches from floor and close to the CO2 source 2 Put the SEU on the panel holder making sure that they are connected tightly 3 Fix another panel holder in a suitab...

Страница 6: ...Alarm Level Lock Lock Unlock User cannot adjust the alarm levels when Locked Default is Lock 1 Press Up Enter button for 10 seconds 2 Change to Advance Mode by press Mode and choose Alm Mode 3 Press Up Down to set Alm level Lock or Unlk 4 Press Enter to Save 9 3 Barometric compensation On Off Default is On Unit automatically compensates for barometric pressure altitude 1 Press Up Enter button for ...

Страница 7: ...nit ºC ºF Press Up to switch between ºC and ºF Select Barometric hPa inHg Press Down to switch between hPa and inHg 10 1 Using the DIAG function Will test the communication link from SEU RDU 1 Press Mode until the DIAG icon flashes 2 Press Enter the SEU s five LEDs will blink and the buzzer will sound 3 The RDU s five LEDs will blink and buzzer will sound simultaneously 10 2 Checking the AL1 CO2 T...

Страница 8: ...0 alarm level 4 Press Enter again to save the setting after selection or press Mode to quit the setting 10 4 Setting the AL3 3rd CO2 Alarm Level parameter User configurable 1 Press Mode until the AL3 CO2 icon flashes 2 Press Enter the AL3 icon shows on LCD Default AL3 3 0 3 Press Up Down to go through 2 0 2 5 3 0 3 5 4 0 alarm level 4 Press Enter again to save the setting after selection or press ...

Страница 9: ...opening on the top left hand corner 2 Open the gas regulator Flow rate should be between 0 15 0 50 liters per minute 3 Wait until the CO2 reading on the SEU settles consistently at or near 0ppm CO2 4 Press the Mode button 5 times the CO2 and CALI icon will start flashing on the SEU 5 Press Enter to view the calibration settings The SEU screen will now display a flashing ZEro and CO2 6 Press Enter ...

Страница 10: ...e able to remain exposed without risk of electric shock 4 Please take care of cable connection between SEU and RDU Make sure the cable from SEU Output RDU port is connected to the RDU INPUT SEU RDU port 5 The dry contact relays do not provide power to external devices like a ventilation fan If there is no power supply to the fan the relay will not work This may result in potential danger with high...

Страница 11: ... Accuracy 1 5 C 2 7 F when CO2 level is below first alarm level Response Time 20 30 minutes case must equalize with environment Operating Conditions Temperature 0 C to 50 C 32 F to 122 F Humidity Range 0 95 RH non condensing Storage Conditions Storage Temperature 20 C to 60 C 4 F to 140 F Power Supply Power Supply DC 9 32VDC 12 32VDC recommended 2A AC adapter Input 100 240 VAC 50 60Hz 0 6A Output ...

Страница 12: ...5 flash Fault LED blink Power on again or press reset button if the Er5 always appear please contact CO2Meter 3 Er7 Internal Data Transmission Error Er7 flash Fault LED blink Er7 flash Fault LED Blink Check the RJ45 plug is connected into the INPUT port of RDU if the Er7 displays on the RDU only Press reset button on SEU or power cycle the unit 15 Support Warranty Contact us We re here to help If ...