USER MANUAL
Multi CO2 Sensor System
CM-7000
Страница 1: ...USER MANUAL Multi CO2 Sensor System CM 7000...
Страница 2: ...obe Tower 7 SV 1029 30 7 Installation 8 Wall Mounting Instructions 8 CM 7005 Main Tablet CM 7003 Sensor CM 7002 Remote and CM 7006 Mini Display Tablet 8 Tablet Installation 9 CM 7003 Sensor Unit Insta...
Страница 3: ...k from the Sensor Page 18 Adjusting Alarm Settings 19 19 Group Configuration 20 Creating Group 20 Adding Sensors to a Group 21 Adjusting Group Settings 22 Relay Operation and Connection CM 7005 CM 700...
Страница 4: ...of pairing programmable relays These relays are preset to be triggered at 5 000ppm TWA 5 000ppm 1 5 and 3 to meet OSHA NIOSH standards This system was designed to adhere to local fire codes in regard...
Страница 5: ...secondary tablet designed for remote display only The gas readings and safety alarm status mirror to this display for viewing purposes Note The CM 7006 is for viewing only This tablet does not offer c...
Страница 6: ...s CAT5 Un Powered Uplink Ethernet Connector Used for Troubleshooting Only USB Type A Connector Used for Troubleshooting and Updates Only QTY 3 10A Relays CM 7003 CO2 Sensor CO2 Measurement Non Dispers...
Страница 7: ...Tablet Input 48V 1 0A Data Rate 10 1000Mbps CM 1026 6 Strobe Tower 24 V DC 6 2m Cable included Length 11 5 long Diameter each 1 5 Alarms set to match 3 relays on RAD units user configurable Mounting b...
Страница 8: ...003 Sensor CM 7002 Remote and CM 7006 Mini Display Tablet Step 1 Use the included wall bracket to mark hole locations Be sure to use included wall anchors for a secure mount Step 2 Install the bracket...
Страница 9: ...and CM 7002 units Connect them ONE AT A TIME using port 1 4 on the back of the tablet See diagram on page 10 Back of CM 7005 DO NOT MOVE ON TO CONNECT THE NEXT UNIT UNTIL THE PREVIOUS IS DISPLAYED ON...
Страница 10: ...rn strobe cover together with a tamper proof screw Step 6 Install Ethernet Cable to the Sensor Unit Strobe port CM 7002 Remote Installation Please Note Not included in standard CM 7000 Package Step 1...
Страница 11: ...ctions o If more than 5 CM 7004 horn Strobes are to be connected to a single port a CM 7009 POE power injector is needed If more than 5 horn strobes are connected to a single port without the use of a...
Страница 12: ...ugh all Sensors and remotes Main Groups Page Without any Groups Create The Main Groups page displays all groups created by the user Groups are created to assign alarm configuration to multiple sensors...
Страница 13: ...ts horn 3 Press Tests both strobe and horn 4 Press End test REMOVE Press this button to remove the sensor form the main Sensors Page This can only be done to an offline sensor Individual Remote Page P...
Страница 14: ...sword co2meter prior to changing them The Tablet Firmware Version can be found by scrolling to the bottom of this page The Firmware Version is the most important piece of information needed while trou...
Страница 15: ...up Alarm 1 4 can all be customized on this page for that group An offline alarm can be set from this page to indicate if a sensor or remote goes offline and fails to communicate with the tablet Other...
Страница 16: ...e follow the following steps Step 1 Power on your CM 7000 CM 7005 Tablet and navigate to the main sensor page This page displays all sensors and remote units that are connected Step 2 Press the settin...
Страница 17: ...or configuration Option 1 Unlock from System Settings Page Step 1 Navigate to the main sensor page This page displays all sensor and remote units that are connected Step 2 Press the setting icon locat...
Страница 18: ...on a sensor icon on the display This will open the senor page on your tablet Step 3 Press the lock icon in the top right hand corner of the display Step 4 The user will be prompted to Insert Passcode...
Страница 19: ...for Denver CO and is a key driven shut off box to mute the alarm until the fire marshal can evaluate the situation Sensors This option allows the user to choose if only the compromised sensor will al...
Страница 20: ...open the System Settings page displayed below First begin by unlocking the Group System settings screen Press the lock icon located in the top right hand corner and enter the password co2meter Next pr...
Страница 21: ...the Group Settings screen by pressing the lock icon located in the top right hand corner and enter the password co2meter A list of all available sensors will appear A Check box will be shown on the s...
Страница 22: ...over that group s icon Once the desired Group has been selected the following settings screen will be displayed The settings must be unlocked prior to adjusting The password is co2meter Each group fe...
Страница 23: ...that can be set to inactive normally open or active normally closed These settings and feature must be unlocked using the password co2meter prior to changing them Press done to save configuration Tabl...
Страница 24: ...arm 3 The relays that can be set to inactive normally open or active normally closed These settings and feature must be unlocked using the password co2 meter prior to changing them Press done to save...
Страница 25: ...the calibration will begin and takes 1 minute 4 Leave the flex tube of Nitrogen on the sensor orifice for the entire minute 5 When calibration is complete the Red Alarm LED on the Remote Sensor Unit w...
Страница 26: ...rt 5 The dry contact relays do not provide power to external devices like a ventilation fan If there is no power supply to the fan the relay will not work This may result in potential danger with high...
Страница 27: ...using the information below For further information on the CM 7000 visit our FAQ page here Support CO2Meter com 386 256 4910 M F 9 00am 5 00pm EST www CO2Meter com See CO2Meter Inc Terms Conditions a...