C.M.C. n.v. - Airmaster S1 installation guide – V1.2 – MANY0402A.00
6.4 Digital inputs
There are 8 digital inputs on the S1 unit: 1 for the emergency stop button, 6 general
purpose and 1 PTC input.
Connector X04
PTC1
1
9
X04
C+
ES
C1
C2
C3
C4 C5
C6
C7
C8
pin
1
C+
Common
pin
2
C1
Input
1
pin
3
C2
Input
2
pin
4
C3
Input
3
pin
5
C4
Input
4
pin
6
C5
Input
5
pin
7
C6
Input
6
pin
8
C7
Input
7
pin
9
C8
Input
8
Common Terminal
Voltage
24VDC
Sink Current
up to 200mA
Digital Input 1 (Emergency Stop)
Sink Current
10mA max
Resistance closed contact
< 3 ohm
Resistance open contact
> 750 Kohm
Digital Inputs 2 to 7 (general purpose)
Sink Current
10mA max
Resistance closed contact
< 13 Kohm
Resistance open contact
> 750 Kohm
Digital Input 8 (PTC thermistor)
Sink Current
1.4mA
Resistance closed contact
< 750 ohm
Resistance open contact
> 4000 ohm
Conformity
IEC 34-11-2, VDE 0660
Note: all resistance are inclusive the resistance of the cabling.