Climax CTC-1052-QT-DT35AW Скачать руководство пользователя страница 43

40 

 

<EXAMPLE> 

With the phone number 

0987654321

, the format 

should  either  INCLUDE  or  EXCLUDE  Contry 
Code, which is “

886

” for Taiwan as below: 

Step 4.

 

Remove the  SIM  card from  the  Mobile 
phone and insert it back into SIM Card 
holder on Panel. 

A.  If  the  Phone  Number  Format  EXCLUDES 

Country Code, please skip this section. 

B.  If  the  Phone  Number  Format  INCLUDES 

Country  Code,  please  proceed  to  SMS 
Remote Program and send in this format: 

 

PROG 1111 REPLA:

886&0”

 

 

Where: 

 

PROG

 = SMS Keyword 

 

1111

 = Access Code 

 

REPLA

 = SMS command for Country Code 

 

886

 = number to be replaced 

 

0

 = number to substitute 

 

After this is completed, Country Code “886” 
will be replaced by “0”. 

 

5.1.9. Temperature 

 

1052-QT-DT35AW 

can 

learn 

in 

temperature sensor, which allows the Panel 
to  report  to  CMS  when  high  or  low 
temperature is detected. 

 

When  temperature  reaches  or  rises  above 
the  High  Temperature  threshold  (default 
95°F/35°C),  the  panel  will  send  High 
Temperature report to CMS. 

After 

High 

Temperature 

report, 

if 

temperature  drops  under  95°F/35°C,  the 
panel  will  send  High  Temperature  Restore 
report to CMS. 

 

When temperature reaches or drops below 
the  Low  Temperature  threshold  (default 
47°F/8.3°C),  the  panel  will  report  Low 
Temperature Alarm to CMS. 

After 

Low 

Temperature 

report, 

if 

temperature  rises  above  47°F/8.3°C,  the 
panel  will  send  Low  Temperature  Restore 

report to CMS. 

 

5.2. Alarm Activation 

 

When an alarm is triggered, CTC-1052-QT-
DT35AW  will  enter  the  Guard  Time  Delay 
period  (see  Command  42).  The 

Help 

Button

 red backlight will turn on. 

 

During  the  Guard  Time  period,  
pressing  the 

Reset  Button

  on  CTC-

1052-QT-DT35AW  will  stop  alarm 
reporting and return to Idle Mode. 

 

If  the  Guard Time  Delay  is  set  as 

00

,  

CTC-1052-QT-DT35AW 

will 

dial 

immediately. 

 

An  alarm  report  can  be  canceled  anytime 
by  pressing  the 

Reset  Button

  on  CTC-

1052-QT-DT35AW. 

 

Call Progress Tone  

 

 

Once  Guard  Time  Delay  expires,  CTC-
1052-QT-DT35AW will summon help based 
on  the  programmed  reporting  method.  If 
Call  Progress  Tone  is  set  as  On,  dailing 
tones will be heard once the CTC-1052-QT-
DT35AW goes off-hook. 

 

Guard Time Delay

 

 

Guard  Time  Delay  time  is  a  time  period 
programmed  to  delay  alarm  reporting  (by 
command  #42).  If  a  false  alarm  is  raised, 
the  user  can  cancel  the  alarm  before  the 
Control Panel starts reporting. 

 

Emergency  alarms  activated  by  Smoke 
Detectors 

(SD), 

Carbon 

Monoxide 

Detectors  (CO),  Carbon  Dioxide  Detector 
(CO2),  Temperature  Sensor  (TS),  and 
Water  Sensors  (WS)  do  not  have  Guard 
Time  Delay  and  will  be  reported 
immediately.  CTC-1052-QT-DT35AW  will 
play  voice  prompt  “Fire  Alarm,”  “Carbon 
Monoxide  Alarm,”  “Water  Leak  Alarm”  to 
inform the user of the alarm at hand. 

 

During  this  time  period,  Control  Panel  will 
play  a  voice  prompt  “Emergency  call  was 
pressed” to alert the user(s). 

<NOTE> 

 

The Guard Time Delay triggered from a 

INCLUDE

  

Country Code 

+886987654321 

EXCLUDE 

Country Code 

0987654321 

Содержание CTC-1052-QT-DT35AW

Страница 1: ...CTC 1052 QT DT35AW User Manual Dec 18 2020...

Страница 2: ...____________________________4 3 Remove the Devices 5 3 1 Command Removing ______________________________________________________5 3 2 Local Removing ___________________________________________________...

Страница 3: ...Method 42 5 2 4 Report Sequence 43 5 3 Walk Test Range Test ____________________________________________________44 5 3 1 In Learning Mode 44 5 3 2 In Walk Test Mode 44 5 3 3 In Idle Mode 44 5 4 Global...

Страница 4: ...ing During or at the end of conversation press once to terminate two way voice communication 4 Microphone 5 Cellular Signal Strength Indicator 6 Orange LED Off Normal Cellular Network connection On Ce...

Страница 5: ...opriate AC voltage rating to prevent component damage A DC 12V output and 1A switching power adapter is generally used to power CTC 1052 QT DT35AW In addition to the adapter there is a rechargeable ba...

Страница 6: ...and Local Firmware Update cable CTC 1052 QT DT35AW has a QT cable A for PC programming and a QT cable B for Local firmware update optional items sold separately To perform PC programming the QT cable...

Страница 7: ...Press and hold the Learn Button of the CTC 1052 QT DT35AW When pressed the CTC 1052 QT DT35AW will emit one beep sound initially and then emit a double beep on the 6th second followed by a voice promp...

Страница 8: ...Programming Mode SMS programming and PC Programming Mode 4 1 Remote Programming Mode To allow Remote Programming there are two options for CTC 1052 QT DT35AW to answer the incoming calls 1 Auto Answe...

Страница 9: ...programming phone set Short beep Command succeeded Long beep Command failed 4 Function Selection According to different Command you will have different entering in this part e g Tel Number Account num...

Страница 10: ...p enter telephone number followed by You can hear one beep from the telephone speaker that indicates the programming is successful If you hear CTC 1052 QT DT35AW emit one beep instead that means the p...

Страница 11: ...th Tel s 124 1st 3rd 4th Tel s 134 2nd 3rd 4th Tel s 234 1st 2nd 3rd 4th Tel s 1234 1st 2nd 3rd 4th Tel 5th GPRS s 12345 1st 2nd 3rd 4th Tel 5th 6th GPRS s 123456 NOTE The Tel number selected in Comma...

Страница 12: ...en in but call recipient can press DTMF keys to open two way communication or change modes If any of SMS Reporting Methods is selected Once alarm or emergency data is successfully transmitted the CTC...

Страница 13: ...ult is set as 1 OFF Command 37 AC Fault Report The CTC 1052 QT DT35AW can be programmed to send a Fault Report when an AC power failure is detected Function Selection Result 0 OFF Send No Report 1 ON...

Страница 14: ...g CTC 1052 QT DT35AW can be programmed to auto answer incoming phone calls after a pre set number of rings have been reached The number of rings range from 00 no auto answer to 32 rings Function Selec...

Страница 15: ...ressing the Reset Button on CTC 1052 QT DT35AW or 2 Movement detected by PIR Detector 3 Only workable by entering 2 digits When Mobility Timer expires and no reset signal is received CTC 1052 QT DT35A...

Страница 16: ...5AW will reset the Off Set timer Command 49 Supervision This option is used to enable system Supervision function Once enabled CTC 1052 QT DT35AW will be able to receive the check in signals from Wris...

Страница 17: ...ncentration value reaches or exceeds the Alarm Reporting threshold CTC 1052 QT DT35AW will report CO2 Alarm to CMS Function Selection Result 0000 9999 0 9999 ppm Factory Default is set as 0800 800ppm...

Страница 18: ...0 instant reporting to 99 seconds During this time period a continuous series 1 beep every 0 5 second of beeps will be emitted to alert user If a false alarm is triggered by a fall detection it can be...

Страница 19: ...s Learning can only be completed within the signal reception range of CTC 1052 QT DT35AW If no signal is received within 20 secs CTC 1052 QT DT35AW will emit a long beep and automatically returns to P...

Страница 20: ...p will be heard for termination Once the Factory Default Reset is executed all the programmed data is returned to its default value and all the devices that have been learnt in are removed You have to...

Страница 21: ...RS1 6 GPRS2 123456 06 Telephone number for status report STARP PROG 1111 STARP 1234 To select then number for status report 1 Telephone 1 2 Telephone 2 3 Telephone 3 4 Telephone 4 5 GPRS1 6 GPRS2 56 1...

Страница 22: ...mode 0 Silent mode On 1 Silent mode Off 1 Silent mode Off 37 AC fault report ACRPT PROG 1111 ACRPT 1 To enable disable AC fault report 0 Disable 1 Enable 1 Enable 38 Follow On Call Back FOLON PROG 111...

Страница 23: ...the two way mode Mic 3 66 Set guard time for fall sensor FAGUD PROG 1111 FAGUD 15 To set the guard time delay time for fall sensor 00 Instant 01 99 1 99 seconds 15 sec 77 Speech report ack SPACK PROG...

Страница 24: ...3000 hfs_server 52dtab04a bin 63488 _ Voice Prompt Download V1URL PROG 1111 V1URL URL File_Name Account To Update Voice Prompt URL Domain Name File_Name EN ES RU AR XX EN English ES Spanish RU Russian...

Страница 25: ...to power supply Press the power button to power on the panel Step 2 Plug the PC Programming cable into the Programming Telephone Jack of the panel Step 3 Connect the PC Programming cable to the USB Ex...

Страница 26: ...QT DT35A Tool programming software open your browser and type below URL in the address bar https www climax com tw climax download 1052qt dt35aw html Step 7 1052 QT DT35A Tool is a portable applicati...

Страница 27: ...DT35AW after installing the USB Driver the USB port connected to CTC 1052 QT DT35AW enter the password default 1111 and then click Open Step 9 A Read All command success message will pop up Click OK a...

Страница 28: ...m reporting method for each Tel Number 1st 4th Tel by selecting from each drop down menu respectively Available reporting methods include Speech and SMS CID 05 To select the number for alarm report Se...

Страница 29: ...vider for your GPRS password If no Password is required you may skip this step IP Address Central Monitoring Station server IP 000 000 000 000 to 255 255 255 255 Port Number Central Monitoring Station...

Страница 30: ...to confirm 31 Ringer Enable for Incoming Calls When disabled CTC 1052 QT DT35AW will operate silent for an incoming call When enabled CTC 1052 QT DT35AW will sound a ring tone as an audio alert for a...

Страница 31: ...er any incoming phone calls from the Monitoring Center 40 Set Access Code The Access Code is used to enter Programming Menu and the Call Back Function It consists of 4 digits and has been set to 1111...

Страница 32: ...CMS is able to receive the report from the Panel accurately After this test report is sent the Control Panel will then send reports at regular interval based on the setting of the Periodic Test Call 4...

Страница 33: ...will not hear the dialing tone of phone calls This function will be disabled if Silent Mode Command 35 is enabled or alarm activation is made from a Silent Device learnt using Command 93 77 Speech Re...

Страница 34: ...he Start button besides 93 Silent Device or the Start Button besides 94 Device to enter learning mode a Panel in learning mode Please press Device Button message will pop up Step 2 Press the Device Bu...

Страница 35: ...mmand success will pop up 81 Remove Zone 1 Device Click Remove to remove zone 1 device from CTC 1052 QT DT35AW A message Remove Zone 1 Device command success will pop up 82 Remove Zone 2 Device Click...

Страница 36: ...t For example if a number string 321 is programmed CTC 1052 QT DT35AW will instantly pick up any call that has 321 as the last 3 digits If a number string 17605851848 is programmed CTC 1052 QT DT35AW...

Страница 37: ...ahrenheit 32 F 212 F Factory Default is 47 F 4 4 1 8 CO2 The CO2 tab allows user to program the CO2 Alarm Reporting threshold When CO2 concentration value reaches or exceeds the Alarm Reporting thresh...

Страница 38: ...different tabs will show the current values of each setting If you select a different profile from the drop down menu the Current Setting profile will disappear to indicate the 1052 QT Tool is no long...

Страница 39: ...with a different name by clicking Save Profile As A pop up window will prompt you to enter the new profile name After entering the profile name and clicking OK the new profile will be saved Apply pro...

Страница 40: ...ase see pictures below as examples When you use another computer to execute the 1052 QT Tool and you wish to apply the configurations of the profiles you created on the old computer please make sure t...

Страница 41: ...Auto Answer Numbers If a user calls the Control Panel using an auto answer number the Control Panel will pick up the call and instantly open up a two way communication with the caller The Control Pan...

Страница 42: ...es CTC 1052 QT DT35AW will emit a voice prompt reminder Inactivity timer expiring please reset every 5 minutes to notify the user for 30 minutes When the Mobility timer is not reset after 30 minutes C...

Страница 43: ...e Restore report to CMS 5 2 Alarm Activation When an alarm is triggered CTC 1052 QT DT35AW will enter the Guard Time Delay period see Command 42 The Help Button red backlight will turn on During the G...

Страница 44: ...ur GPRS username If no username is required you may skip this step Password offered by your SIM card service provider Please inquire your service provider for your GPRS password If no Password is requ...

Страница 45: ...adjusted value will be kept for the next communication Press any DTMF key except the designated hang up keys to reset the communication time to its preset duration Please note that when a particular D...

Страница 46: ...report destination for a maximum of 4 times 2 Control Panel will try all report destinations for up to 15 times in total 3 If more than 1 report destinations are set to a report method e g GPRS the p...

Страница 47: ...D CO IR WS Step 2 Move the device to your desirable location in the house and press the TEST button of the device to observe the range of its operation Step 3 If CTC 1052 QT DT35AW responds with one l...

Страница 48: ...the programming and learn in the devices one by one again 6 Appendix 6 1 CID Event Code The message composition for CID Event code is in the form ACCT MT QXYZ GG C1C2C3 And is explained in the followi...

Страница 49: ...n previously NOTE This event code will be sent with a fixed zone number of 072 339 Medication Non Adherence When the scheduled dose is still not taken after Time for Medicine alarm expires default 30...

Страница 50: ...47 641 Mobility When CTC 1052 QT DT35AW makes Mobility Timer Expired reporting NOTE This event code will be sent with a fixed zone number of 071...

Страница 51: ...number 11 Bi 4 or 6 or 8 digits Account number 1 Tel Number 1 Bi No account number 12 Bi 4 or 6 or 8 digits Account number 2 Tel Number 2 Bi No account number 13 Bi 4 or 6 or 8 digits Account number 3...

Страница 52: ...Threshold 032 200 F Bi 95 F 56 Bi Low Temperature Reporting Threshold 032 200 F Bi 47 F 57 Bi CO2 Alarm Reporting Threshold 0 9999ppm Bi 800ppm 63 Bi Set Speaker Volume Enter Mode Number Speaker Volu...

Страница 53: ...nt into the Control Panel Door Sensor Played once when the sensor has been learnt into the Control Panel Water Leak Sensor Played once when the sensor has been learnt into the Control Panel Emergency...

Страница 54: ...e received including interference that may cause undesired operation 3 This device should be installed and operated with a minimum distance of 20 centimeters between the radiator and your body 4 The a...

Отзывы: