C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S
Vertical DOAS
R e v. : 0 1 / 3 1 / 1 3
28
C l i m a t e M a s t e r Wa t e r - S o u r c e H e a t P u m p s
System Start-up Report -
A copy of the system start up
report can be found in the back of this manual. This report
needs to be fi lled out thoroughly by a qualifi ed service
technician and returned to ClimateMaster for warranty
validation. Please ensure that the model and serial
number of the unit is noted on this form. The model and
serial number can be found on the systems rating plate
located on or near the electrical compartment service
door. Failure to complete and return this form will void
the units warranty. These reports are also helpful when
trying to correct existing problems. Should you need
system diagnosis help, fax the completed worksheet to
the ClimateMaster Service Department using the number
provided. Be sure to include your name and a telephone
number where you can be reached.
Start-up Supervision Supplemental Information
(Optional) -
A ClimateMaster factory startup is required
to be purchased with the equipment. A factory startup
includes several key services:
• The expertise of an accomplished, factory-trained
mechanic who will supervise the commissioning of
the equipment.
• This ClimateMaster representative will assist the
installing contractor with filling out the Startup Report.
• He will also inspect the installation to make sure that
the DOAS unit has been properly integrated with the
rest of the equipment on the jobsite.
• Finally, he can train the maintenance personnel to
operate and service the equipment if necessary.
A factory start up does not include installation assistance.
The installing contractor is responsible for ensuring that
the system is ready for startup when the ClimateMaster
representative arrives.
When the installing contractor is confi dent the system
will be ready, he should contact the ClimateMaster Sales
representative to schedule the startup. Please call at
least two weeks before the desired startup date to help
prevent scheduling confl icts.
Refrigeration System Operating Pressures -
Many
factors affect the operating pressures on a given day. Such
factors include ambient temperature, air fl ow volume, and
relative humidity. The following ranges are typical:
Tranquility Models:
• HFC-410A Normal suction pressure range: 85 to
150 psig
• HFC-410A Normal discharge pressure range: 300
to 500 psig
Note: Always check the system air fl ow before you
troubleshoot the refrigeration circuit.