Page 10 of 15
Rev. G
INSTALLATION AND OPERATION
SITE WIRING AND PREPARATION
Wiring from the WD-02.2 to the CLiC Glass panel should be run prior to the CLiC Glass panel installation. All wiring
must be performed in accordance with the applicable building codes and electrical wiring requirements as denoted
for Class 3 systems of the National Electric Code (NEC). All wiring should be completed by a qualified and
experienced technician.
Placement:
The WD-02.2 should be installed within an appropriate NEMA enclosure in a accessible area within
sufficient distance to plug the power supply into a standard 120vac outlet. The WD-02.2 and the power supply are
both mountable if desired. Please allow adequate space for ventilation and heat dissipation around the devices.
N
OTE
:
I
N THE EVENT THAT THESE DEVICES ARE INSTALLED WITHIN AN AIR
-
EXCHANGE SPACE
(
PLENUM AIRWAY
)
THEY
SHALL BE MOUNTED WITHIN AN APPROPRIATE CERTIFIED
P
LENUM
-
SAFE ENCLOSURE OF MINIMUM SIZE GREATER THAN
273
X
100
X
138
MM
.
Wire Type and Connections
Shielded two-conductor wire must be used for all wire connections on the WD-02.2 Glass Controller. This is
important to maintain FCC compliance and to minimize the chance for electrical interference.
I
MPORTANT
:
When
completing the terminal connections, the shield of eac
h wire run must be terminated to the ‘Ground’ terminals on
the WD-02.2 and left unconnected at the CLiC Glass panel and at the trigger switch or relay devices.
Wire Size and Maximum Length
The shielded wire utilized for connections on the WD-02.2 shall be a minimum of 18 AWG. It is important that the
correct gauge wire is used to assure the correct voltage and signal reaches the CLiC Glass panel. The maximum
wire distance between the WD-02.2 and the CLiC Glass panel is 100 meters (328 feet).