Testing:
Once connected to the 240V mains supply, the unit must be allowed to charge the battery for at least 24
hours. Conduct the following tests:
•
For the first test, the emergency lamp must remain illuminated for at least 2 hours after
disconnection from the mains supply.
Subsequent tests require the unit to illuminate for at least 90 minutes. The results of all tests are
required to be recorded in a service logbook, which is to be kept on-site at all times. If the unit fails to
remain illuminated for the requisite time, remedial action must be taken to repair the situation and once
completed, the unit must pass a subsequent test. For more specific information, please refer to the
current edition of the AS 2293.3 Standard.
Trouble Shooting:
Below are a list of common problems and their possible causes.
Fault:
The Green LED indicator is not illuminated.
Check: A.C. is connected and is turned on.
Battery is connected
Test Switch for damage.
Fault:
Lamp does not illuminate in emergency mode.
Check: A.C. is connected.
Lamp is correctly inserted.
Battery is connected
Fault:
Lamp illuminates in emergency mode, but only stays on for a short period.
Check:
Battery has been allowed to charge for at least 24 hours.
Battery for damage.
Fault:
Green LED flashes once every 5seconds - Battery is disconnected
Check:
Battery is connected.
Fault:
Green LED blinks off once every 5 seconds - Charging very flat battery
Action:
Allow 20min to recover battery then recheck
Fault:
Green LED flashes at 2Hz (Fast flash) - Faulty battery
Action:
Replace battery
Rated Emergency Lumen Output in accordance with AS2293.1 (refer
to spacing tables for installation positions):
Refer to the Technical Label for classification information.
Trade Series Boxlite LED Exit
Installation & Maintenance Instruction Leaflet
Wall Mount
Ceiling Mount
Victoria (Head Office & Manufacturing)
Website:
Email:
Phone:
+61 3 9559 2700
Fax:
+61 3 9559 2799
New South Wales
Phone:
+61 2 8805 6400
Fax:
+61 2 8805 6444
Queensland
Phone:
+61 7 3442 9700
Fax:
+61 7 3442 9777
South Australia/Northern Territory
Phone:
+61 8 8301 8800
Fax:
+61 8 8351 8286
Western Australia
Phone:
+61 8 9207 0000
Fax:
+61 8 9207 0088
New Zealand
Phone:
+64 800 548 448
Designed in Australia to comply with the requirements
of AS2293.3: 2005 and AS/NZS CISPR15: 2017
Models:
EBLLED-xx-xx
EBLLED-WM-LI
Economy Lithium Boxlite LED Exit
– Wall Mount
EBLLED-CM-LI
Economy Lithium Boxlite LED Exit
– Ceiling Mount
Spare Parts:
1560200
Battery, Eco Lithium, 3.2V 1.1Ah
8002715
PCA: Duris LED Strip CT10276
8002971
PCA: EBLLED-LI #CT10614-L1 6C32 M/NM CF
Important:
It is illegal for anyone, except for a licensed electrician to install or maintain this product. Before installation,
ensure that the electricity supply has been switched off and isolated. Installation must be carried out in
accordance with the relevant Australian and International Standards.