Cleveland Controls AFS–442 Скачать руководство пользователя страница 1

Bulletin AFS442.02

1

Model

AFS–442

Air  Pressure Sensing Switch with Adjustable Set Point Range

Dimensions in Inches

(Millimeters)

Application

The 

Model AFS-442 

is a general pur-

pose  proving switch designed for
package burner, furnace, fuel-burning
equipment, HVAC and other Energy
Management applications. It may be
used to sense positive, negative, or
differential air pressure.

General Description &

Operation

The plated housing contains a dia-
phragm, a calibration spring and a
snap-acting SPDT

 

switch.The sample

connections located on each side of
the diaphragm accept 

1

/

8

" pipe.

An enclosure cover guards against ac-
cidental contact with the live switch
terminal screws and the set point ad-
justing screw. The enclosure cover will
accept a ½" conduit connection.

Mounting (see Figure 1)

Select a mounting location which is
free from vibration. The 

AFS-442

 must

be mounted with the diaphragm in any

Cleveland Controls

Division of UniControl Inc.

(Figure 2)

(Figure 1)

vertical plane in order to obtain the
lowest specified operating set point.
Avoid mounting with the sample line
connections in the "up" position. Sur-
face mount via the two 

3

/

16

" diameter

holes in the integral mounting bracket.
The mounting holes are 3-

7

/

8

" apart.

Air Sampling  Connection

(see Figure 2)

The 

AFS-442 

is equipped with two

1

/

8

" – 27 NPT female connectors. For

sample lines of up to 10 feet, 

1

/

8

" pipe

is acceptable. For lines up to 20 feet,
use ¼" pipe. For lines up to 60 feet,
use ½" pipe.  For each right angle
bend, add 4 feet to the computed
sample line length to determine correct
pipe size.For sample lines of up to 10
feet, ¼" OD tubing is acceptable. For
lines up to 20 feet, use ¼" ID tubing.
For lines up to 60 feet, use ½" ID tub-
ing. Locate the sampling probe a  mini-

mum of  1-½ duct diameters down-
stream from the air source. Install the
sampling

 

probe as close to the center

of the airstream as possible. Refer to
Figure 2 to identify the high pressure
inlet  (H) and the low pressure inlet
(L). Select one of the five application
options listed below (on page 2), and
connect the sample lines as recom-
mended.

Отзывы: