M. Maintenance
A maintenance program avoids unnecessary downtime, costly repairs, and promotes safety. It is
recommended that a record be maintained of daily, weekly, monthly, and yearly maintenance activities.
Electrical and mechanical devices require systematic and periodic inspection and maintenance. Any
“automatic” features do not relieve the operator from responsibility, but rather frees him from certain repetitive
chores, providing time for upkeep and maintenance.
Unusual noise, improper gauge reading, leak, sign of overheating, etc. can indicate a developing malfunction
requiring corrective action.
ONLY FACTORY AUTHORIZED BURNER SERVICE PERSONNEL SHOULD START UP, ADJUST, OR
SERVICE THE EQUIPMENT.
ANY COVER PLATES, ENCLOSURES, OR GUARDS ANCHORED TO THE BURNER, OR ANY BURNER
RELATED EQUIPMENT, MUST REMAIN IN POSITION AT ALL TIMES. ONLY DURING MAINTENANCE
AND SERVICE SHUTDOWN CAN THESE COVER PLATES, ENCLOSURES, OR GUARDS BE ALLOWED
TO BE REMOVED. THEY MUST BE REPLACED, AND SECURELY ANCHORED BEFORE TESTING,
ADJUSTING, OR RUNNING THE BURNER OR BURNER RELATED EQUIPMENT.
CONTROL SYSTEM
Most operating controls require very little maintenance beyond regular inspection. Examine electrical
connections. Keep the controls clean. Remove any dust from the interior of the control. Covers should be left
on controls at all times. Keep the control cabinet doors closed. Dust and dirt can damage motor starters and
relay contacts. Starter contacts are plated with silver and are not harmed by discoloration. Never use files or
abrasive materials such as sandpaper on contact points.
PROGRAMMING CONTROL
This control requires no adjustment, nor should any attempt be made to alter contact settings or timing logic.
Those programmers with contacts may require occasional cleaning. If so, follow instructions given in the
manufacturer ’s bulletin. Never use abrasive materials. The manufacturer ’s bulletin also contains
troubleshooting information. The flame detector lens should be cleaned as often as conditions demand.
A periodic safety check procedure should be established to test the complete safeguard system. Tests should
verify safety shutdown with a safety lockout upon failure to ignite the pilot or the main flame, and upon loss
of flame. Each of these conditions should be checked on a scheduled basis. The safety check procedures are
contained in the manufacturer’s bulletin.
!
DANGER
WARNING
!
DANGER
WARNING
Содержание FLX 1000
Страница 12: ...Chapter 1 General Description 1 6 750 177...
Страница 68: ...Chapter 2 Profire V Burner 2 56 750 177...
Страница 90: ...Chapter 4 Sequence of Operation 4 10 750 177...
Страница 104: ...Chapter 5 Adjustment Procedures 5 14 750 177...
Страница 110: ...Chapter 6 Troubleshooting 6 6 750 177...
Страница 122: ...8 2 750 177 Figure 8 1 Typical Hot Water Flextube Casing...
Страница 124: ...8 4 750 177 Figure 8 2 Typical Low Pressure Steam Flextube Casing...
Страница 126: ...8 6 750 177 Figure 8 3 Typical High Pressure Steam Flextube Casing...
Страница 128: ...Parts Chapter 8 8 8 750 177 Steam Pressure Controls...
Страница 129: ...Chapter 8 Parts 750 177 8 9 Water Level Controls...
Страница 130: ...Parts Chapter 8 8 10 750 177 Water Level Controls continued...
Страница 131: ...Chapter 8 Parts 750 177 8 11 Water Column Main and Aux 15 Steam...
Страница 132: ...Parts Chapter 8 8 12 750 177 Water Column Main and Aux 150 Steam...
Страница 133: ...Chapter 8 Parts 750 177 8 13 Safety Valves...
Страница 134: ...Parts Chapter 8 8 14 750 177...
Страница 135: ......
Страница 136: ...e mail info cleaverbrooks com Web Address http www cleaverbrooks com...