background image

44000070 Iss 03

 

 

Consort Equipment Products Ltd 

Registered Office:  Thornton Industrial Estate 
Milford Haven, Pembrokeshire, SA73 2RT 
Tel:  01646 692172 

Fax:  01646 695195 

 

BS EN ISO 9001 Registered Company No FM12671

 

 

 

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS FOR

 

Heat-Zone 

Fan Heater 

FOR WIRELESS CONTROLS 

Catalogue Numbers: HE7010W-30 3 kW 230/240V 

 

 

PLEASE RETAIN THIS LEAFLET FOR FUTURE MAINTENANCE 

MODEL 

Heat-Zone is a quiet Fan Heater designed for Commercial and 
Industrial situations, and is suitable for mounting on the wall.  
The Heat-Zone incorporates a tangential flow fan and the unit is 
designed to operate in free air conditions.  It is important that 
there should be no restriction on the free flow of air through the 
unit. When installed the top of the heater case should be a 
minimum of 200mm from the ceiling. 

 

MOUNTING 

The normal mounting height is 2.3m above the floor, although 
this will depend to some extent on the situation.   
 
The heater can be positioned to blow air at any angle, from 
horizontal to vertically downwards, subject to the conditions 
mentioned below.  It is suggested that an angle of 45

0

 is a 

convenient starting point when setting up the unit. 
 
It must always be installed with the axis of the motor horizontal. 
Failure to ensure this will result in excessive bearing wear and 
premature failure. 
 
A mounting bracket is provided for mounting on a wall. 
 
The heater should not be mounted in situations where it may be 
subject to conditions of excessive humidity or the atmosphere is 
corrosive. 
 

INSTALLATION 

To the unit connect a suitable length of 3 or 4 core flexible 
cable to the input terminal block. 
 
Loosen mounting screws, allowing the mounting bracket to be 
removed from the unit.  Making sure that the mounting bracket 
is horizontal, fix the bracket to the wall using 3 x No 8 wood 
screws. 
 
Place the unit on the mounting bracket ensuring the washers are 
spaced as on diagram (a plain washer either side of the 
mounting bracket). 
 
Tighten screws to hold the unit at the required angle. 
 
 

 

 
 

 

 

 
 

 

 

 

ELECTRICAL CONNECTIONS 

These units are suitable for connection to a 230/240V 50Hz 
single phase ac supply.  The units consume 3kW of electrical 
power when the fan and heater are in operation. 
 
To connect a supply to the heater, first remove the top cover by 
unscrewing the 4 fixing screws (2 either side), then lifting off 
the cover.  The input terminal block, marked NFH, is fitted at 
the left hand side of the unit looking from above (at the 
opposite end to the fan motor). 
 
A double-pole isolator switch should be included in the 
installation. 
 

 

 

Отзывы: