UNINTERRUPTIBLE POWER SYSTEM

GLOBAL SN SERIES UPS

1,000VA THROUGH 2,000VA

MODELS:

SN1000
SN1250
SN1500
SN2000

Information contained herein is the property of Clary Corporation, is proprietary, confidential, and not to be disclosed,

disseminated or used except for the purpose provided by

CLARY CORPORATION

P/N 510-12580

A

RD-12/29/03

Manufactured by

T H E   C O N T I N U O U S   P O W E R   C O M P A N Y

Sold Exclusively Through

NOVA POWER SOLUTIONS, Inc.

11367 Sunset Hills Road, Reston, VA 20190

Tel: (703) 742-0000 

 Fax (703) 742-4003

email: [email protected]

Содержание SN1000

Страница 1: ...of Clary Corporation is proprietary confidential and not to be disclosed disseminated or used except for the purpose provided by CLARY CORPORATION P N 510 12580 A RD 12 29 03 Manufactured by T H E C...

Страница 2: ...LE PAGE TABLE OF CONTENTS 1 INTRODUCTION 3 TECHNICAL DESCRIPTION 4 PACKAGING 6 PHYSICAL DESCRIPTION 7 SUMMARY OF INDICATORS AND CONTROLS 11 INSTALLATION 12 OPERATION 13 SIGNALS AND INTERFACING 14 SPEC...

Страница 3: ...nance of the UPS and batteries Be aware of the following symbols and their meaning as they appear throughout the manual This equipment generates and uses radio frequency energy and if not installed an...

Страница 4: ...owing exactly what patterns the supply utility power maintains and by knowing exactly the condition and life expectancy of the battery reserve Reference the block diagram for a simplified explanation...

Страница 5: ...NE EMERGENCY CUTOFF SWITCH VOLTAGE WINDOW DETECTOR COMMON MODE CHOKE RECTIFIER CHARGER POWER FACTOR CORRECTOR DC RAILS MICROPROCESSOR CONTROLLER AC INVERTER GENERATOR LOAD STANDBY BATTERY COMMON MODE...

Страница 6: ...it report this to your carrier These units are encapsulated in a protective wrap that comes apart once the product is removed from the shipping carton Save all packing material for future use Take ext...

Страница 7: ...nhanced to ensure you have a full understanding of the operation of this system Visual indicators used on the front panel are long lasting very efficient light emitting diodes LED When operating the p...

Страница 8: ...rating indicator 11 Bypass indicator 4 Battery Level Charge discharge indicators 12 Alarm Silence switch 5 Load Level Output capacity indicators 13 Fault indicator 6 Cold Start DC start switch 14 Batt...

Страница 9: ...IGNAL Open collector signal contacts 17 INPUT Dual pole circuit breaker 21 RS232 Computer communications signals 18 DC INPUT Auxiliary battery connector 22 IDENTIFICATION LABEL 19 SYSTEM OUTPUT 120VAC...

Страница 10: ...l Rear Panel Callouts 16 INPUT Terminal Block 3 position 20 Signal Open collector signal contacts 17 INPUT BREAKER Dual pole circuit breaker 21 RS232 Computer communications signals 18 DC input Auxili...

Страница 11: ...tility voltage is available it may still be a requirement to initialize some equipment When this switch is pressed in for at least two seconds the system will start up on battery power The SYSTEM ON O...

Страница 12: ...o be stored it is recommended to refresh the internal battery at least once every 90 days To do this plug the system in position the power On Off switch to ON press and hold at least two seconds the L...

Страница 13: ...nates An intermittent audible alarm will sound The SILENCE Switch may be operated at this time it must be held in for at least 2 seconds to quiet the alarm As battery discharge continues in this condi...

Страница 14: ...OLLECTOR CONNECTOR 2 AC INPUT FAIL 3 UPS ON 4 GROUND 5 LOW BATTERY 6 UPS SHUTDOWN 7 UPS SHUTDOWN 8 9VDC RS232 CONNECTOR 1 DCD 2 TX 3 RX 4 DTR 5 SIGNAL GROUND 6 DSR 7 CTS 8 RTS SIGNAL OPEN COLLECTOR CO...

Страница 15: ...ature Controlled Reversible Forced Air Dimensions See Model Selection Guide Weight See Model Selection Guide DESIGN Standard Features Power Factor Corrected Digital Regenerative On Line Sinewave Inver...

Страница 16: ...s 1000 700 1250 875 1500 1050 2000 1400 Input Current Amps 120VAC 7 2 8 8 10 7 14 3 Output Current Amps 8 3 10 4 12 5 16 7 Input Plug Standard NEMA Type 5 15P 5 15P 5 15P 5 20P Battery Backup Time Min...

Страница 17: ...lectrolyte is harmful to the skin and eyes It may be toxic CAUTION A battery can present a risk of electrical shock and high short circuit current The following precautions should be observed when wor...

Страница 18: ...tory In consulting the factory always have the unit model number and serial number at hand This information is located on the identification label and is essential in retrieving your unit s performanc...

Страница 19: ...ive carrier available or via customer s shipping instructions 2 3 The nature of certain equipment installations may be such that it would be impractical or technically infeasible to remove the Clary p...

Страница 20: ...362 8908 Circuit Breaker 363 11043 AC Output Lamp 362 8495 Fuse 15 Amp 250VAC 171 9519 Handle 120 12535 2 Filter Assembly LEVEL II PART NO DESCRIPTION 360 9307 4 Output Terminal Block 4 Position 360 9...

Страница 21: ...ff by the Load On Off switch on the Front panel The Internal Hard Bypass is protected by the Input Circuit Breaker See System Schematic 118 14052 WARNING Whenever UPS has utility power on the input an...