DLP-G763 Install Air Plenum for ONS 15454 M2 Shelf in ANSI 19-inch Configuration
This task installs the air plenum for the ONS 15454 M2 shelf in ANSI 19-inch cabinet
or rack configuration.
Purpose
• #2 Phillips Dynamometric screwdriver
• Medium slot-head screwdriver
• Small slot-head screwdriver
• Screws: #12-24 x 0.50 pan-head Phillips screws (4)
• Wing head screws (4)
• One air plenum kit (horizontal and vertical air plenum)
Tools/Equipment
As needed
Required/As Needed
Onsite
Onsite/Remote
None
Security Level
In the 19-inch rack and cabinet, the air plenum can be mounted only if the minimum opening is 20.600 inches
to install the vertical air plenums behind the front rails.
Note
Procedure
Step 1
Place the horizontal air plenum above the shelf slot in the ANSI 19-inch cabinet or rack.
Step 2
Insert the wing head screws provided with the kit, and tighten to a torque value of 11.5 in-lb (1.3 N-m).
Figure 107: Installing the horizontal air plenum in the ANSI 19-inch configuration
Step 3
Install the vertical air plenum to the left of the horizontal air plenum:
a) Insert the vertical plenum in the free space between the horizontal plenum and cabinet.
Cisco ONS 15454 Hardware Installation Guide
185
Installing the ONS 15454 M2 Shelf
DLP-G763 Install Air Plenum for ONS 15454 M2 Shelf in ANSI 19-inch Configuration
Содержание ONS 15454
Страница 2: ... 2019 Cisco Systems Inc All rights reserved ...
Страница 16: ...Cisco ONS 15454 Hardware Installation Guide xvi Contents ...
Страница 28: ...Cisco ONS 15454 Hardware Installation Guide xxviii Preface Preface ...
Страница 36: ...Cisco ONS 15454 Hardware Installation Guide 6 Overview Cisco ONS 15454 M6 Shelf ...
Страница 510: ...Cisco ONS 15454 Hardware Installation Guide 480 Hardware Specifications Dimensions ...