17-5
Cisco ONS 15454 SDH Procedure Guide, R7.0
78-17194-01
Chapter 17 DLPs D1 to D99
DLP- D5 Mount the Shelf Assembly in a Rack (One Person)
Figure 17-1
Mounting an ONS 15454 SDH in a Rack
Step 3
Using the hex tool that shipped with the assembly, install the two set screws into the holes that will not
be used to mount the shelf. Let the set screws protrude sufficiently to hold the mounting brackets.
Step 4
Lift the shelf assembly to the desired position in the rack.
Step 5
Align the screw holes on the mounting brackets with the mounting holes in the rack.
Step 6
Using the Phillips screwdriver, install one mounting screw in each side of the assembly.
Step 7
When the shelf assembly is secured to the rack, install the remaining mounting screws.
Note
Use at least one set of the horizontal screw slots on the ONS 15454 SDH to prevent slippage.
Step 8
Using the hex tool, remove the temporary set screws.
Step 9
Return to your originating procedure (NTP).
61240
FAN
FAIL
CRIT
MAJ
MIN
Equipment rack
Содержание ONS 15454 SDH
Страница 26: ...Tables vi Cisco ONS 15454 SDH Procedure Guide R7 0 78 17194 01 ...
Страница 62: ...xxii Cisco ONS 15454 SDH Procedure Guide R7 0 78 17194 01 About this Guide ...
Страница 64: ...xxiv Cisco ONS 15454 SDH Procedure Guide R7 0 78 17194 01 About this Guide ...
Страница 66: ...xxvi Cisco ONS 15454 SDH Procedure Guide R7 0 78 17194 01 About this Guide ...
Страница 414: ...16 4 Cisco ONS 15454 SDH Procedure Guide R7 0 78 17194 01 Chapter 16 Power Down the Node NTP D114 Power Down the Node ...
Страница 832: ...A 14 Cisco ONS 15454 SDH Procedure Guide R7 0 78 17194 01 Appendix A CTC Information and Shortcuts Equipment Inventory ...
Страница 860: ...Index IN 28 Cisco ONS 15454 SDH Procedure Guide R6 0 78 17194 01 ...