1-75
Cisco ONS 15454 DWDM Procedure Guide, R8.0
78-17704-02
Chapter 1 Install the Shelf and Common Control Cards
NTP- G15 Install the Common Control Cards
Figure 1-33
Y-Cable Module
Step 5
Repeat Steps
through
as necessary for each Y-cable module you want to install.
Step 6
Return to your originating procedure (NTP).
NTP-G15 Install the Common Control Cards
Warning
During this procedure, wear grounding wrist straps to avoid ESD damage to the card. Do not directly
touch the backplane with your hand or any metal tool, or you could shock yourself.
Statement 94
Caution
Always use the supplied ESD wristband when working with a powered ONS 15454. Plug the wristband
cable into the ESD jack located on the lower-right outside to edge of the shelf assembly.
Note
If protective clips are installed on the backplane connectors of the cards, remove the clips before
installing the cards.
Purpose
This procedure describes how to install the common control cards.
Tools/Equipment
Redundant TCC2/TCC2P cards (required)
AIC-I card (optional)
MS-ISC-100T (optional; for multishelf node configurations)
Prerequisite Procedures
NTP-G7 Install the Power and Ground, page 1-32
NTP-G14 Install DWDM Equipment, page 1-67
Required/As Needed
Required
Onsite/Remote
Onsite
Security Level
Provisioning or higher