B-8
Cisco ONS 15200 Installation, Setup, and Test Manual
78-13765-01
Appendix B Acceptance Test Plan
B.4 ONS 15200 System Span Test
Note
The comparison between measured and expected values is only relevant when the fiber has been
characterized.
Table B-15 ONS 15201 SCU Client Transmit Data
CLIP
Serial Number
Measured Client
Transmit Power (dBm)
Pass or Fail
Valid Range
-8 to -10 dBm
Table B-16 ONS 15201 CLIP Switchmode
CLIP
Serial Number
Switchmode
Table B-17 ONS 15200 System Span Test Procedure Checklist
Related
Step in
Chapter 4
Description
Pass
Fail
BER test error-free for 2 hours — unprotected
BER test error-free for 2 hours — A-side
BER test error-free for 2 hours — B-side
Table B-18 ONS 15200 Hub Span DWDM Transmit and Receive Measurements
ONS
15252 MCU
Slot #
ITU
Channel
OSA
Measured
DWDM A
Side Tx
OSA
Measured
DWDM A
Side Rx
OSA
Measured
DWDM B
Side Tx
OSA
Measured
DWDM B
Side Rx