Cisco Nexus 9364C ACI-Mode Switch Hardware Installation Guide

First Published: 

2017-07-31

Last Modified: 

2017-10-05

Americas Headquarters

Cisco Systems, Inc.
170 West Tasman Drive
San Jose, CA 95134-1706
USA
http://www.cisco.com
Tel: 408 526-4000
       800 553-NETS (6387)
Fax: 408 527-0883

Содержание Nexus 9364C

Страница 1: ...rdware Installation Guide First Published 2017 07 31 Last Modified 2017 10 05 Americas Headquarters Cisco Systems Inc 170 West Tasman Drive San Jose CA 95134 1706 USA http www cisco com Tel 408 526 4000 800 553 NETS 6387 Fax 408 527 0883 ...

Страница 2: ...e encouraged to try to correct the interference by using one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio TV technician for help Modifications to this product no...

Страница 3: ...s 5 Altitude Requirements 6 Dust and Particulate Requirements 6 Minimizing Electromagnetic and Radio Frequency Interference 6 Shock and Vibration Requirements 7 Grounding Requirements 7 Planning for Power Requirements 7 Airflow Requirements 8 Rack and Cabinet Requirements 9 Clearance Requirements 10 C H A P T E R 3 Installing the Chassis 11 Install a Rack 11 Unpacking and Inspecting a New Switch 1...

Страница 4: ... Setting Up an Optional Console Interface 35 Setting Up an Optional Management Connection 36 Maintaining Transceivers and Optical Cables 36 C H A P T E R 5 Replacing Components 37 Replacing a Fan Module During Operations 37 Replacing a Power Supply Module 39 Removing an AC Power Supply 39 Removing an HVAC HVDC Power Supply 40 Removing a DC Power Supply 41 Installing an AC Power Supply 41 Installin...

Страница 5: ...ecifications 53 Power Cable Specifications for AC Power Supplies 53 HVAC HVDC Power Cables Supported by ACI Mode and NX OS Mode Switches 54 DC Power Cable Specifications 55 Regulatory Standards Compliance Specifications 55 A P P E N D I X C LEDs 57 Switch Chassis LEDs 57 Fan Module LEDs 58 Power Supply LEDs 58 A P P E N D I X D Additional Kits 59 Accessory Kit 59 Rack Mount Kit 60 A P P E N D I X ...

Страница 6: ...Cisco Nexus 9364C ACI Mode Switch Hardware Installation Guide vi Contents ...

Страница 7: ...riptions use the following conventions Description Convention Bold text indicates the commands and keywords that you enter literally as shown bold Italic text indicates arguments for which the user supplies the values Italic Square brackets enclose an optional element keyword or argument x Square brackets enclosing keywords or arguments separated by a vertical bar indicate an optional choice x y B...

Страница 8: ...ments for which you supply values are in italic screen font italic screen font Nonprinting characters such as passwords are in angle brackets Default responses to system prompts are in square brackets An exclamation point or a pound sign at the beginning of a line of code indicates a comment line Related Documentation The Application Centric Infrastructure documentation set includes the following ...

Страница 9: ...eference NX OS Release 11 0 Cisco Verified Scalability Guide for Cisco ACI Cisco ACI MIB Quick Reference Cisco Nexus CLI to Cisco APIC Mapping Guide Application Centric Inftrastructure Fabric Hardware Installation Guide Cisco NX OS Release Notes for Cisco Nexus 9000 Series ACI Mode Switches Cisco Nexus 9000 Series ACI Mode Licensing Guide Cisco Nexus 93108TX EX ACI Mode Switch Hardware Installatio...

Страница 10: ...hes documentation is available at https www cisco com c en us support switches nexus 9000 series switches tsd products support series home html Cisco Application Virtual Switch Documentation The Cisco Application Virtual Switch AVS documentation is available at https www cisco com c en us support switches application virtual switch tsd products support series home html Documentation Feedback To pr...

Страница 11: ... module with burgundy coloring NXA FAN 160CFM PI Power supply modules two one for operations and one for redundancy 1 1 with the following choices 1200 W port side exhaust AC power supply with blue coloring NXA PAC 1200W PE 1200 W port side intake AC power supply with burgundy coloring NXA PAC 1200W PI 1200 W HVAC HVDC dual direction airflow power supply with white coloring N9K PUV 1200W 930 W por...

Страница 12: ...onment ENV LEDs 1 Screw holes for center mount bracket two post rack installations 5 1 10 Gigabit SFP ports 2 2 Notch on both sides of the chassis for locking the power supply end of the chassis to the bottom support rails four post rack installations 6 40 100 Gigabit QSFP28 ports 64 3 To determine which transceivers adapters and cables are supported by this switch see the Cisco Transceiver Module...

Страница 13: ...modules with port side intake or port side exhaust airflow For port side intake airflow the fan and AC power supply modules have burgundy coloring For port side exhaust airflow the fan and AC power supplies have blue coloring You can also order the 1200 W HVAC HVDC power supply which has dual direction airflow with white coloring Dual direction airflow modules automatically use the airflow directi...

Страница 14: ...the other modules in the switch Note If the switch has port side intake airflow burgundy coloring for fan modules you must locate the ports in the cold aisle If the switch has port side exhaust airflow blue coloring for fan modules you must locate the ports in the hot aisle If you locate the air intake in a hot aisle the switch can overheat and shut down Caution Cisco Nexus 9364C ACI Mode Switch H...

Страница 15: ...temperature must be between 40 to 158 degrees Fahrenheit 40 to 70 degrees Celsius Humidity Requirements High humidity can cause moisture to enter the switch Moisture can cause corrosion of internal components and degradation of properties such as electrical resistance thermal conductivity physical strength and size The switch is rated to operate at 8 to 80 percent relative humidity with a humidity...

Страница 16: ...frequency interference RFI from the switch can adversely affect other devices such as radio and television TV receivers operating near the switch Radio frequencies that emanate from the switch can also interfere with cordless and low power telephones Conversely RFI from high power telephones can cause spurious characters to appear on the switch monitor RFI is defined as any EMI with a frequency ab...

Страница 17: ...ansients or spikes can erase data from memory or cause components to fail To protect against these types of problems ensure that there is an earth ground connection for the switch You can connect the grounding pad on the switch either directly to the earth ground connection or to a fully bonded and grounded rack When you properly install the chassis in a grounded rack the switch is grounded becaus...

Страница 18: ...switch For the power cables to use with the power supplies see Power Cable Specifications on page 53 Note Airflow Requirements The switch is designed to be positioned with its ports in either the front or the rear of the rack depending on your cabling and maintenance requirements Depending on which side of the switch faces the cold aisle you must have fan and power supply modules that move the coo...

Страница 19: ...ng per section 1 of the ANSI EIA 310 D 1992 standard The depth of a four post rack must be 24 to 32 inches 61 0 to 81 3 cm between the front and rear mounting rails for proper mounting of the bottom support brackets or other mounting hardware Required clearances between the chassis and the edges of its rack or the interior of its cabinet are as follows 4 5 inches 11 4 cm between the front of the c...

Страница 20: ...lowing figure Depth of the chassis 5 Chassis 1 Maximum extension of the bottom support rails 6 Vertical rack mount posts and rails 2 Depth of the front clearance area this equals the depth of the chassis 7 Chassis width 3 Width of the front clearance area this equals the width of the chassis with two rack mount brackets attached to it 4 Both the front and rear of the chassis must be open to both a...

Страница 21: ...bolted to the floor before you slide the unit out for servicing Failure to stabilize the rack can cause the rack to tip over Warning Step 2 If the rack has bonded construction connect it to the earth ground This action enables you to easily ground the switch and its components and to ground your electrostatic discharge ESD wrist strap to prevent damaging discharges when you handle ungrounded compo...

Страница 22: ...at you have received all of the ordered items The shipment should include the following Switch chassis which includes the following installed components Two power supplies any combination of the following with the airflow direction being the same as for the fan modules 1200 W AC power supply NEBS compliant Port side exhaust airflow with blue coloring NXA PAC 1200W PE Port side intake airflow with ...

Страница 23: ...pplies with their airflow direction set by the fan modules For port side exhaust airflow the switch must have port side exhaust fan and AC power supply modules with one or more of the following colorings Blue coloring on fan modules and AC power supplies White coloring on 1200 W HVAC HVDC power supplies dual direction airflow power supplies with their airflow direction set by the fan modules You c...

Страница 24: ...oad the rack from the bottom to the top with the heaviest component at the bottom of the rack If the rack is provided with stabilizing devices install the stabilizers before mounting or servicing the unit in the rack Before You Begin You must separately order the center mount brackets if you are installing the chassis in a two post rack These brackets do not ship with the chassis unless you specif...

Страница 25: ...e chassis near the top of the rack with the power supply and fan modules in the appropriate aisle for their required airflow If the fan modules have a blue coloring for port side exhaust airflow then you must position the modules by the cold aisle If the fan modules have a burgundy coloring for port side intake airflow you must position the modules by the hot aisle Power supply modules must have t...

Страница 26: ...ensure that the system remains stable The following guidelines are provided to ensure your safety Warning This unit should be mounted at the bottom of the rack if it is the only unit in the rack When mounting this unit in a partially filled rack load the rack from the bottom to the top with the heaviest component at the bottom of the rack If the rack is provided with stabilizing devices install th...

Страница 27: ...to the chassis before mounting the chassis in the rack Attaching the Bottom Support Rails to the Rack The switch chassis that you are installing ships with two adjustable bottom support rails that you can attach to a four post rack to hold the chassis Each of these bottom support rails has two pieces one that slides into the other so that you can adjust them to fit racks with front and rear mounti...

Страница 28: ...cal mounting rails on the rack Statement 1006 Chassis Warning for Rack Mounting and Servicing To prevent bodily injury when mounting or servicing this unit in a rack you must take special precautions to ensure that the system remains stable The following guidelines are provided to ensure your safety Warning This unit should be mounted at the bottom of the rack if it is the only unit in the rack Wh...

Страница 29: ...panding bottom support rails to the other side of the rack Check the two installed bottom support rails to be sure that both have their chassis stops by the same aisle either both by the hot aisle or both by the cold aisle and that both rails are level and level with each other If they are not level adjust the higher rail down to the level of the lower rail Note What to Do Next You are ready to in...

Страница 30: ...end locks onto the chassis stops at the end of the rails and so that the front mount brackets on the chassis come into contact with the front mount rails on the rack Statement 1074 Comply with Local and National Electrical Codes Installation of the equipment must comply with local and national electrical codes Warning Statement 1032 Lifting the Chassis To prevent personal injury or damage to the c...

Страница 31: ... unit should be mounted at the bottom of the rack if it is the only unit in the rack When mounting this unit in a partially filled rack load the rack from the bottom to the top with the heaviest component at the bottom of the rack If the rack is provided with stabilizing devices install the stabilizers before mounting or servicing the unit in the rack Step 1 Slide the power supply end of the chass...

Страница 32: ...sle required for the fan and power supply modules 2 Step 2 Use a customer supplied rack mount screw an M6 x 10 mm screw or other appropriate screw for the rack to attach each of the two mounting brackets on the chassis to the rack and tighten each screw to the appropriate torque setting for the screw for M6 x 10 mm screws use 40 in lbs 4 5 N m of torque Grounding the Chassis The switch chassis is ...

Страница 33: ...ng or replacing the unit the ground connection must always be made first and disconnected last Warning Before You Begin Before you can ground the chassis you must have a connection to the earth ground for the data center building Step 1 Use a wire stripping tool to remove approximately 0 75 inch 19 mm of the covering from the end of the grounding wire Step 2 Insert the stripped end of the groundin...

Страница 34: ...69 N m of torque Powering Up the Switch To power up the switch you must connect the power supplies to one or two power sources The number of power sources used depends on the type of power redundancy that you require as follows For no power redundancy connect only the power supplies to one power source For n 1 redundancy connect the power supplies to one or two power sources For n n redundancy con...

Страница 35: ...ower Cable Specifications on page 53 connect the C13 plug on the power cable to the power receptacle on the power supply 2 Rotate the cable retention clip on the power supply over the C13 plug to prevent accidental unplugging of the cable 3 Connect the other end of the power cable to the AC power source 4 Verify that the LED is on and green If the LED is off check the AC power source circuit break...

Страница 36: ...ower supply is powered by a different power source Note Connecting an HVAC HVDC power supply 1 Using the recommended power cable for your country or region see Power Cable Specifications on page 53 insert the Saf D Grid connector on the power cable to the power receptacle on the power supply until it clicks in place 2 Connect the other end of the power cable to the power source If connecting to an...

Страница 37: ...g the terminals when the power is on 4 Turn the power on at the circuit breaker 3 Verify that the LED is on and green If the LED is off check the AC power source circuit breaker to be sure that it is turned on Cisco Nexus 9364C ACI Mode Switch Hardware Installation Guide 27 Installing the Chassis Powering Up the Switch ...

Страница 38: ...Cisco Nexus 9364C ACI Mode Switch Hardware Installation Guide 28 Installing the Chassis Powering Up the Switch ...

Страница 39: ...entric Infrastructure Controller APIC appliance cluster of APICs Leaf switches Cisco Nexus 93108TC EX 93108TC FX 93120TX 93128TX 93180LC EX 93180YC EX 93180YC FX 9332PQ 9348GC FXP 9372PX 9372PX E 9372TX 9372TX E 9396PX and 9396TX switches Spine switches Cisco Nexus 9336PQ 9364C 9504 9508 and 9516 switches As shown in the following figure each APIC is connected to one or two leaf switches and each ...

Страница 40: ...t In situations where long parallel cable runs cannot be separated by at least 3 3 feet 1 meter we recommend that you shield any potential noise sources by housing them in a grounded metallic conduit Note The optical transceivers that are not already assembled to their cables come separate from their cables To prevent these transceivers and their cables from being damaged we recommend that you kee...

Страница 41: ...pect fiber ends under a microscope to determine if damage has occurred Connecting Leaf Switches to APICs You must downlink one or two recommended for redundancy ACI mode leaf switches Cisco Nexus 93108TC EX 93108TC FX 93120TX 93128TX 93180LC EX 93180YC EX 93180YC FX 9332PQ 9348GC FXP 9372PX 9372PX E 9372TX 9372TX E 9396PX or 9396TX to each Application Policy Infrastructure Controller APIC in your ...

Страница 42: ...bles insert the transceiver on the cable into a downlink optical port on a leaf switch For a 10GBASE T copper cable insert the RJ 45 connector on the cable into a downlink BASE T port on a leaf switch To determine which transceivers and cables are supported by this switch see http www cisco com c en us support interfaces modules transceiver modules products device support tables list html Note Con...

Страница 43: ...uplink module 1 For 10 Gigabit support use a QSFP to SFP adapter such as CVR QSFP SFP10G with a SFP or SFP transceiver The following table lists the number of ports that you can connect on each ACI mode line card installed in a modular spine switch Cisco Nexus 9504 9508 or 9516 switch or on each Cisco Nexus 9336PQ or 9364C spine switch The number of line cards in a spine switch depends on the mode...

Страница 44: ...ot view directly with optical instruments Warning Statement 1055 Class I and Class 1M Laser Class I CDRH and Class 1M IEC laser products Warning Statement 1056 Unterminated Fiber Cable Invisible laser radiation may be emitted from the end of the unterminated fiber cable or connector Do not view directly with optical instruments Viewing the laser output with certain optical instruments for example ...

Страница 45: ... spine switch in the network The fabric automatically implements Equal Cost Multi Pathing ECMP and enables all links You do not need to configure the links Setting Up an Optional Console Interface You can optionally set up a console interface for performing the initial configuration of the To do this use the interface cable provided in the accessory kit to connect the to your console device You ca...

Страница 46: ...intenance guidelines Transceivers are static sensitive To prevent ESD damage wear an ESD preventative wrist strap that is connected to the grounded chassis Do not remove and insert a transceiver more often than is necessary Repeated removals and insertions can shorten its useful life Keep all optical connections covered when not in use Clean them before using to prevent dust from scratching the fi...

Страница 47: ...e switch make sure that the fan modules are positioned in one of the following ways For port side exhaust airflow with blue coloring position the fan modules in a cold aisle For port side intake airflow with burgundy coloring position the ports in a cold aisle Before You Begin Before you can replace a fan module ensure that both of the following conditions exist There are two functioning fan modul...

Страница 48: ...es the airflow direction of the other fan and AC power supply modules already installed in the chassis Port side intake airflow is indicated with burgundy coloring and port side exhaust airflow is indicated with blue coloring Power supplies with dual direction airflow airflow direction is set by the fan modules have white coloring Note c Position the fan module in front of the open fan slot be sur...

Страница 49: ...rflow direction used by the switch see the coloring of the fan modules The following list describes the power supplies supported by this switch N9K PAC 1200W PE 1200 W port side exhaust blue latch power supply requiring an AC power source N9K PAC 1200W PI 1200 W port side intake burgundy latch power supply requiring an AC power source N9K PUV 1200W 1200 W dual direction white latch high voltage AC...

Страница 50: ... HVDC Power Supply You can remove one power supply while the other one provides power to the switch To disconnect the power supply from its power cables you must shut off the power from the power source and then either disconnect a connector for the power cables or release each of three cables from the power supply requires a standard screw driver Step 1 Turn off the circuit breaker for the power ...

Страница 51: ...t to Do Next You are ready to install a DC power supply in the open slot Installing an AC Power Supply You can replace one power supply while the other one provides power to the switch Before You Begin The power supply that you are installing must be capable of using the same airflow direction as the fan trays installed in the same switch and it must use the same type of power source as the other ...

Страница 52: ...able is attached to the appropriate power source for the power supply Depending on the outlet receptacle on your power distribution unit you might need the optional jumper cable to connect the switch to your outlet receptacle Note Step 5 Verify that the power supply is operational by making sure that the power supply LED is green For information on what the power supply LEDs indicate see Power Sup...

Страница 53: ...ctrical cables have not been connected to the electrical connector block wire them as described in Wiring a 48 V DC Electrical Connector Block on page 44 Step 4 Make sure that the other end of the power cable is connected to the appropriate power source for the power supply Step 5 If using a DC power source turn on the circuit breaker for the DC power source connected to the power supply Step 6 Ve...

Страница 54: ...ical connector block wire them as described in Wiring a 48 V DC Electrical Connector Block on page 44 Step 3 Turn on the circuit breaker for the DC power source connected to the power supply Step 4 Verify that the power supply is operational by making sure that the power supply LED is green For information on what the power supply LEDs indicate see Power Supply LEDs on page 58 Wiring a 48 V DC Ele...

Страница 55: ...Step 5 Use a small screwdriver to depress the spring loaded wire retainer lever on the lower spring cage wire connector Insert your green ground wire into the aperture and then release the lever Step 6 Use a small screwdriver to depress the spring loaded wire retainer lever on the middle spring cage wire connector Insert your black DC negative wire into the aperture and then release the lever Step...

Страница 56: ...Cisco Nexus 9364C ACI Mode Switch Hardware Installation Guide 46 Replacing Components Installing a DC Power Supply ...

Страница 57: ...0 to 40 C Standard perforated cabinets Solid walled cabinets with a roof fan tray bottom to top cooling Standard open racks If you are selecting an enclosed cabinet we recommend one of the thermally validated types either standard perforated or solid walled with a fan tray Note We do not recommend that you use racks that have obstructions such as power strips because the obstructions could impair ...

Страница 58: ...ts Specific to Standard Open Racks If you are mounting the chassis in an open rack no side panels or doors ensure that the rack meets the following requirements The minimum vertical rack space per chassis must be two rack units RUs equal to 3 5 inches 8 8 cm The distance between the chassis air vents and any walls should be 2 5 inches 6 4 cm Requirements Specific to Perforated Cabinets A perforate...

Страница 59: ...ower Cable Specifications page 53 Regulatory Standards Compliance Specifications page 55 Environmental Specifications Specification Environment 32 to 104 F 0 to 40 C Ambient operating temperature Temperature 40 to 158 F 40 to 70 C Ambient non operating 8 to 80 with humidity gradation of 10 per hour 5 to 95 Operating Non operating Relative humidity 0 to 13 123 feet 0 to 4 000 meters Operating Altit...

Страница 60: ...0 W DC port side exhaust blue NXA PDC 1200W PE 930 W DC port side intake burgundy NXA PDC 1200W PI Transceiver and Cable Specifications To determine which transceivers adapters and cables are supported by this switch see https www cisco com c en us support interfaces modules transceiver modules products device support tables list html To see the transceiver specifications and installation informat...

Страница 61: ...ations These specifications apply to the following 1200 W AC power supplies NXA PAC 1200W PE NXA PAC 1200W PI Specification Characteristic Nominal range 100 120 VAC 200 240 VAC AC input voltage Nominal range 50 to 60 Hz Range 47 63 Hz AC input frequency 10 A at 100 120 VAC 8 A at 200 240 VAC Maximum AC input current 800 W at 100 120 VAC 1200 W at 200 240 VAC Maximum output power per power supply 1...

Страница 62: ...pply 12 VAC at 100 A 12 VDC at 100 A Power supply output voltage For 200 to 277 VAC For 192 to 400 VDC 12 V at 2 5 A Power supply standby voltage Climate Savers Platinum Efficiency 80Plus Platinum certified Efficiency rating RSP1 Form factor 930 W DC Power Supply Specifications These specifications apply to the following power supplies NXA PDC 930W PE NXA PDC 930W PI Specification Characteristic N...

Страница 63: ...ription Power Cord Part Number Locale Power Cord Jumper C13 C14 Connectors 6 6 feet 2 0 m CAB C13 C14 2M Power cord C13 to C14 recessed receptacle 10 A 9 8 feet 3 m CAB C13 C14 AC Cabinet jumper power cord 250 VAC 10 A C14 C13 connectors 2 3 feet 0 7 m CAB C13 CBN 250 V 10 A 8 2 feet 2 5 m CAB 250V 10A AR Argentina 250 VAC 10 A 3112 plug 8 2 feet 2 5 m CAB 9K10A AU Australia 250 V 10 A 6 9 feet 2 ...

Страница 64: ...wer cord included with switch NO POWER CORD All except Argentina Brazil and Japan HVAC HVDCPowerCablesSupportedbyACI ModeandNX OSModeSwitches Cord Set Description PowerCordPartNumber Power Type 2 foot 0 6 m cable with Saf D Grid and SD connectors CAB HVAC SD 0 6M HVAC 6 6 foot 2 0 m cable with Saf D Grid and C14 connector use for up to 240 V CAB HVAC C14 2M HVAC 2 foot 0 6 m cable with Saf D Grid ...

Страница 65: ...C 930W PE port side exhaust airflow NXA PDC 930W PI port side intake airflow No power cord included with switch NO POWER CORD All except Argentina Brazil and Japan Regulatory Standards Compliance Specifications The following table lists the regulatory standards compliance for the switch Table 1 Regulatory Standards Compliance Safety and EMC Description Specification Products should comply with CE ...

Страница 66: ...s standards in all configurations except when you use more than 40 pluggable optics of Cisco part number 10 3142 01 or 10 3142 02 Note EMC Emissions EN55024 CISPR24 EN300386 KN 61000 4 series EMC Immunity The product is RoH 6 compliant with exceptions for leaded ball grid array BGA balls and lead press fit connectors RoHS Cisco Nexus 9364C ACI Mode Switch Hardware Installation Guide 56 System Spec...

Страница 67: ...in the chassis Flashing blue BCN This switch is not being identified Off The switch is operational Green STS The switch is booting up Flashing amber Temperature exceeds minor alarm threshold Amber Temperature exceeds major alarm threshold Red The switch is not receiving power Off Fans and power supply modules are operational Green ENV At least one fan or power supply module is not operating Amber ...

Страница 68: ... supply is on and outputting power to the switch Off Green Power supply is connected to a power source but not outputting power to the switch power supply might not be installed in the chassis Off Flashing green Power supply is not receiving power Off Off Power supply warning possibly one of the following conditions High voltage High power Low voltage Power supply installed in chassis but not conn...

Страница 69: ...ory kit Quantity Description Illustration 1 Console cable with DB 9F and RJ 45F connectors 1 kit Ground lug kit Two hole lug 1 M4 x 8 mm Phillips pan head screws 2 1 ESD wrist strap disposable 1 EAC Compliance document Not applicable 1 Hazardous substances list for customers in China Not applicable Cisco Nexus 9364C ACI Mode Switch Hardware Installation Guide 59 ...

Страница 70: ... reseller you might receive additional contents in your kit such as documentation hardware and power cables Note For a list of the available power cables see Power Cable Specifications on page 53 Rack Mount Kit Quantity Part 2 Front Mount Brackets 2 Center Mount Brackets 2 Bottom Support Rails 8 M4 screws Cisco Nexus 9364C ACI Mode Switch Hardware Installation Guide 60 Additional Kits Rack Mount K...

Страница 71: ...ssful switch operation ventilation and accessibility The following table lists the site planning tasks that we recommend that you complete before you install the switch Your completion of each task ensures a successful switch installation Verification Time and Date Planning Activity Space evaluation Space and layout Floor covering Impact and vibration Lighting Physical access Maintenance access En...

Страница 72: ... circuits for power redundancy UPS for power failures Grounding proper wire gauge and lugs Circuit breaker size Grounding evaluation Data center ground Cable and interface equipment evaluation Cable type Connector type Cable distance limitations Interface equipment transceivers EMI evaluation Cisco Nexus 9364C ACI Mode Switch Hardware Installation Guide 62 Site Preparation and Maintenance Records ...

Страница 73: ... person Contact phone Contact e mail Building site name Data center location Floor location Address line 1 Address line 2 City State Provence Contact person ZIP postal code Country Chassis and Module Information Use the following worksheet to record information about the switch Contract number Cisco Nexus 9364C ACI Mode Switch Hardware Installation Guide 63 Site Preparation and Maintenance Records...

Страница 74: ...ress Gateway router address DNS address Use the following worksheet to record information about the modules in the switch Notes Module Serial Number Module Type Module Slot Fan module 1 Fan module 2 Fan module 3 Power Supply 1 Power Supply 2 Cisco Nexus 9364C ACI Mode Switch Hardware Installation Guide 64 Site Preparation and Maintenance Records Chassis and Module Information ...