Cisco Nexus 9300-FX Скачать руководство пользователя страница 1

Cisco Nexus 9348GC-FXP ACI Mode Hardware Installation Guide

First Published:

2017-09-27

Last Modified:

2018-03-01

Americas Headquarters

Cisco Systems, Inc.
170 West Tasman Drive
San Jose, CA 95134-1706
USA
http://www.cisco.com
Tel: 408 526-4000

800 553-NETS (6387)

Fax: 408 527-0883

Содержание Nexus 9300-FX

Страница 1: ...dware Installation Guide First Published 2017 09 27 Last Modified 2018 03 01 Americas Headquarters Cisco Systems Inc 170 West Tasman Drive San Jose CA 95134 1706 USA http www cisco com Tel 408 526 4000 800 553 NETS 6387 Fax 408 527 0883 ...

Страница 2: ... are encouraged to try to correct the interference by using one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio TV technician for help Modifications to this product...

Страница 3: ...A P T E R 2 Temperature Requirements 5 Humidity Requirements 5 Altitude Requirements 5 Dust and Particulate Requirements 6 Minimizing Electromagnetic and Radio Frequency Interference 6 Shock and Vibration Requirements 7 Grounding Requirements 7 Planning for Power Requirements 7 Airflow Requirements 8 Rack and Cabinet Requirements 9 Clearance Requirements 10 Installing the Switch Chassis 11 C H A P...

Страница 4: ... Setting Up an Optional Console Interface 31 Setting Up an Optional Management Connection 32 Maintaining Transceivers and Optical Cables 32 Replacing Components 35 C H A P T E R 5 Replacing a Fan Module 35 Removing a Fan Module 35 Installing a Fan Module 36 Replacing a Power Supply Module 36 Replacing an AC Power Supply 36 Rack Specifications 39 A P P E N D I X A Overview of Racks 39 General Requi...

Страница 5: ...er Supplies 44 Regulatory Standards Compliance Specifications 45 LEDs 47 A P P E N D I X C Switch Chassis LEDs 47 Fan Module LEDs 48 Power Supply LEDs 48 Additional Kits 49 A P P E N D I X D Rack Mount Kit for a Two post Rack 49 Rack Mount Kit NXK ACC KIT 1RU 49 Rack Mount Kit N3K C3064 ACC KIT 50 Accessory Kit 50 Site Preparation and Maintenance Records 53 A P P E N D I X E Site Preparation Check...

Страница 6: ...Cisco Nexus 9348GC FXP ACI Mode Hardware Installation Guide vi Contents ...

Страница 7: ...c text indicates arguments for which the user supplies the values Italic Square brackets enclose an optional element keyword or argument x Square brackets enclosing keywords or arguments separated by a vertical bar indicate an optional choice x y Braces enclosing keywords or arguments separated by a vertical bar indicate a required choice x y Nested set of square brackets or braces indicate option...

Страница 8: ...available on Cisco com at the following URL https www cisco com c en us support cloud systems management application policy infrastructure controller apic tsd products support series home html Web Based Documentation Cisco APIC Management Information Mode Reference Cisco APIC Online Help Reference Cisco APIC Python SDK Reference Cisco ACI Compatibility Tool Cisco ACI MIB Support List Downloadable ...

Страница 9: ...rdware Installation Guide Cisco Nexus 93128TX ACI Mode Switch Hardware Installation Guide Cisco Nexus 93180LC EX ACI Mode Switch Hardware Installation Guide Cisco Nexus 93180YC EX ACI Mode Switch Hardware Installation Guide Cisco Nexus 93180YC FX ACI Mode Switch Hardware Installation Guide Cisco Nexus 9332PQ ACI Mode Switch Hardware Installation Guide Cisco Nexus 9336PQ ACI Mode Switch Hardware In...

Страница 10: ...ttps www cisco com c en us support switches application virtual switch tsd products support series home html Documentation Feedback To provide technical feedback on this document or to report an error or omission please send your comments to apic docfeedback cisco com We appreciate your feedback Obtaining Documentation and Submitting a Service Request For information on obtaining documentation usi...

Страница 11: ...xhaust airflow with blue coloring NXA FAN 30CFM F Power supply modules two one for operations and one for redundancy 1 1 with the following choices do not mix AC and DC power sources and do not mix airflow directions 350 W AC power supply with port side intake airflow burgundy coloring NXA PAC 350W PI 350 W AC power supply with port side exhaust airflow blue coloring NXA PAC 350W PE 440 W DC power...

Страница 12: ... rack mounting brackets 6 100 1000 Megabit 1GBASE T host ports 48 3 To determine which transceivers adapters and cables this switch supports see the Cisco Transceiver Modules Compatibility Information document The following figure shows the hardware features seen from the power supply side of the chassis Cisco Nexus 9348GC FXP ACI Mode Hardware Installation Guide 2 Overview Overview ...

Страница 13: ...se less than 2 5 W less than 0 5 A inclusive of surge current Devices such as external hard drives that instantaneously draw more than 0 5 A are not supported Note Depending on whether you plan to position the ports in a hot or cold aisle you can order the fan and power supply modules with port side intake or port side exhaust airflow To determine the airflow direction of the modules installed in ...

Страница 14: ...rflow Otherwise the switch can overheat and shut down If you are installing a dual direction power supply that module automatically uses the same airflow direction as the other modules in the switch Note If the switch has port side intake airflow burgundy coloring for fan modules you must locate the ports in the cold aisle If the switch has port side exhaust airflow blue coloring for fan modules y...

Страница 15: ...h humidity can cause moisture to enter the switch Moisture can cause corrosion of internal components and degradation of properties such as electrical resistance thermal conductivity physical strength and size The switch is rated to withstand from 5 to 95 percent non condensing relative humidity Buildings in which the climate is controlled by air conditioning in the warmer months and by heat durin...

Страница 16: ...he switch monitor RFI is defined as any EMI with a frequency above 10 kHz This type of interference can travel from the switch to other devices through the power cable and power source or through the air as transmitted radio waves The Federal Communications Commission FCC publishes specific regulations to limit the amount of EMI and RFI that can be emitted by computing equipment Each switch meets ...

Страница 17: ... connection to the rack Alternatively you can ground the chassis by using a customer supplied grounding cable that meets your local and national installation requirements we recommend 6 AWG wire for U S installations connected to the chassis with a grounding lug provided in the switch accessory kit and to the facility ground You automatically ground AC power supplies when you connect them to AC po...

Страница 18: ...e and 13A UK Warning For DC input application please refer to the statement below Note Statement 1005 Circuit Breaker This product relies on the building s installation for short circuit overcurrent protection Ensure that the protective devices are rated not greater than 40A when the switch is powered with regular DC power supplies rated 48 60VDC Ensure that the protective devices are rated not gr...

Страница 19: ...ay bottom to top cooling Standard open four post Telco racks Work with your cabinet vendors to determine which of their cabinets meet the following requirements or see the Cisco Technical Assistance Center TAC for recommendations Use a standard 19 inch 48 3 cm four post Electronic Industries Alliance EIA cabinet or rack with mounting rails that conform to English universal hole spacing per section...

Страница 20: ...airflow and maintain the switch For the clearances required for an installation of this chassis in a four post rack see the following figure Depth of the chassis 5 Chassis 1 Maximum extension of the bottom support rails 6 Vertical rack mount posts and rails 2 Depth of the front clearance area this equals the depth of the chassis 7 Chassis width 3 Width of the front clearance area this equals the w...

Страница 21: ...tement 1071 Warning Definition IMPORTANT SAFETY INSTRUCTIONS This warning symbol means danger You are in a situation that could cause bodily injury Before you work on any equipment be aware of the hazards involved with electrical circuitry and be familiar with standard practices for preventing accidents Use the statement number provided at the end of each warning to locate its translation in the t...

Страница 22: ...u are positioning the fan and power supply modules in a cold aisle make sure that the switch has port side exhaust fan modules with blue colorings All fan modules must have the same direction of airflow Installation Guidelines When installing the switch follow these guidelines Record equipment and installation information in the forms presented in Chassis and Module Information as you install and ...

Страница 23: ...for damage or missing components If anything is missing or damaged contact your customer service representative immediately Keep the shipping container in case the chassis requires shipping at a later time Tip Before you begin Before you unpack the switch and before you handle any switch components be sure that you are wearing a grounded electrostatic discharge ESD strap To ground the strap attach...

Страница 24: ...front of the rack is the side easiest to access for maintenance You must supply the eight 10 32 or 12 24 screws required to mount the slider rails and switch to the rack Note Before you begin You have inspected the switch shipment to ensure that you have everything ordered Make sure that the switch rack mount kit includes the following parts Front rack mount brackets 2 Rear rack mount brackets 2 S...

Страница 25: ... end of the chassis 5 Front rack mount bracket aligned to the port end of the chassis 1 Four M4 screws used to attach the bracket to the chassis 6 Four M4 screws used to attach the bracket to the chassis 2 Two M4 screws used to attach the bracket to the chassis 7 Rear rack mount guide aligned to the module end of the chassis 3 Rear rack mount guide aligned to the port end of the chassis 8 Two M4 s...

Страница 26: ... used for the front mount brackets attached to the easiest accessed end of the chassis and the other two posts will have the slider rails b Position a slider rail at the desired level on the back side of the rack and use two 12 24 screws or two 10 32 screws depending on the rack thread type to attach the rails to the rack see the following figure Tighten 12 24 screws to 30 in lb 3 39 N m of torque...

Страница 27: ...alled in the rack Slide the rack mount guides onto the slider rails and then gently slide the switch all the way into the rack until the front rack mount brackets come in contact with two rack or cabinet posts c Holding the chassis level insert two screws 12 24 or 10 32 depending on the rack type in each of the two front rack mount brackets using a total of four screws and into the cage nuts or th...

Страница 28: ...ding pad connect the other end of the wire to the facility ground Installing the Switch into a Two post Rack To install the switch you must attach mounting brackets to the switch and secure the switch to the rack Installation in racks other than 19 inch racks requires a bracket kit not included with the switch The following figure shows the standard 19 inch mounting brackets Cisco Nexus 9348GC FXP...

Страница 29: ...that its ports will be in the cold aisle If the switch has port side exhaust modules fan modules with blue coloring position the switch so that its fan and power supply modules will be in the cold aisle b Position the bracket so that four of its screw holes are aligned to the screw holes on the side of the chassis as shown in the following figure Cisco Nexus 9348GC FXP ACI Mode Hardware Installati...

Страница 30: ...ad screws and tighten each screw to 12 in lb 1 36 N m of torque d Repeat previous step for the other front rack mount bracket on the other side of the switch and be sure to position that bracket the same distance from the front of the switch Cisco Nexus 9348GC FXP ACI Mode Hardware Installation Guide 20 Installing the Switch Chassis Installing the Switch into a Two post Rack ...

Страница 31: ...g cable to the chassis grounding pad and the facility ground Statement 1024 Ground Conductor This equipment must be grounded Never defeat the ground conductor or operate the equipment in the absence of a suitably installed ground conductor Contact the appropriate electrical inspection authority or an electrician if you are uncertain that suitable grounding is available Warning Statement 1046 Insta...

Страница 32: ... out of the crimped lug 2 M4 screws used to secure the grounding lug to the chassis 3 Chassis grounding pad 1 Grounding cable with 0 75 in 19 mm of insulation stripped from one end inserted into the grounding lug and crimped in place 2 Step 3 Secure the grounding lug to the chassis grounding pad with two M4 screws see Callouts 1 and 3 in the previous figure and tighten the screws to 11 to 15 in lb...

Страница 33: ... fully secured in their chassis slots All of the fan slots must be filled with fan modules and the power supply slots must be filled with the same types of power supplies do not mix AC and DC power supplies Step 1 For each AC power supply do the following a Using the recommended AC power cable for your country or region connect one end to the AC power supply b Connect the other end of the power ca...

Страница 34: ... guides you through the basic configuration For instructions on how to configure the switch and check module connectivity see the appropriate Cisco Nexus configuration guide Cisco Nexus 9348GC FXP ACI Mode Hardware Installation Guide 24 Installing the Switch Chassis Starting the Switch ...

Страница 35: ...pplication Centric Infrastructure Controller APIC appliance cluster of APICs Leaf switches Cisco Nexus 93108TC EX 93108TC FX 93120TX 93128TX 93180LC EX 93180YC EX 93180YC FX 9332PQ 9348GC FXP 9372PX 9372PX E 9372TX 9372TX E 9396PX and 9396TX switches Spine switches Cisco Nexus 9336PQ 9364C 9504 9508 and 9516 switches As shown in the following figure each APIC is connected to one or two leaf switch...

Страница 36: ...nt required When running power and data cables in overhead or subfloor cable trays we strongly recommend that you locate power cables and other potential noise sources as far away as practical from network cabling that terminates on Cisco equipment In situations where long parallel cable runs cannot be separated by at least 3 3 feet 1 meter we recommend that you shield any potential noise sources ...

Страница 37: ...he environment In addition clean connectors if they are exposed to dust or accidentally touched Both wet and dry cleaning techniques can be effective refer to your site s fiber optic connection cleaning procedures Do not touch the ends of connectors Touching the ends can leave fingerprints and cause other contamination Inspect routinely for dust and damage If you suspect damage clean and then insp...

Страница 38: ...rface cable to a downlink port on a leaf switch For a Cisco 10GBASE LR or SR transceiver and cable insert the transceiver into a downlink optical port on a leaf switch before connecting the cable to the transceiver For Cisco SFP Active Optical Cables insert the transceiver on the cable into a downlink optical port on a leaf switch For a 10GBASE T copper cable insert the RJ 45 connector on the cabl...

Страница 39: ...372TX Cisco Nexus 9372TX E 40 Gigabits 6 QSFP ports with M6PQ or M4PQ E uplink module Cisco Nexus 9396PX Cisco Nexus 9396TX 10 or 40 Gigabits1 12 QSFP ports with M12PQ uplink module 1 For 10 Gigabit support use a QSFP to SFP adapter such as CVR QSFP SFP10G with a SFP or SFP transceiver The following table lists the number of ports that you can connect on each ACI mode line card installed in a modu...

Страница 40: ...ment 1053 Class 1M Laser Radiation Class 1M laser radiation when open Do not view directly with optical instruments Warning Statement 1055 Class I and Class 1M Laser Class I CDRH and Class 1M IEC laser products Warning Statement 1056 Unterminated Fiber Cable Invisible laser radiation may be emitted from the end of the unterminated fiber cable or connector Do not view directly with optical instrume...

Страница 41: ... network The fabric automatically implements Equal Cost Multi Pathing ECMP and enables all links You do not need to configure the links Setting Up an Optional Console Interface You can optionally set up a console interface for performing the initial configuration of the switch To do this use the interface cable provided in the accessory kit to connect the switch to your console device You can conn...

Страница 42: ...interface cable with LH or SX SFP transceivers can be used for longer connections If you use the management interface connect only one of the two management ports The switch does not support your use of two management ports at the same time Note Step 2 Connect the other end of the cable to an external hub switch or router Maintaining Transceivers and Optical Cables Transceivers and fiber optic cab...

Страница 43: ...cleaning techniques can be effective refer to your site s fiber optic connection cleaning procedures Inspect routinely for dust and damage If you suspect damage clean and then inspect fiber ends under a microscope to determine if damage has occurred Cisco Nexus 9348GC FXP ACI Mode Hardware Installation Guide 33 Connecting the Switch to the ACI Fabric Maintaining Transceivers and Optical Cables ...

Страница 44: ...Cisco Nexus 9348GC FXP ACI Mode Hardware Installation Guide 34 Connecting the Switch to the ACI Fabric Maintaining Transceivers and Optical Cables ...

Страница 45: ...es in air from a cold aisle and exhausts to a hot aisle Otherwise the switch can overheat and shutdown If you are changing the airflow direction of all the modules in the chassis you must shutdown the switch before replacing all the fan and power supply modules with modules using the other airflow direction During operations all of the modules must have the same direction of airflow Caution Removi...

Страница 46: ...quires two power supplies for redundancy With one power supply providing the necessary power for operations you can replace the other power supply during operations so long as the new power supply has the same airflow direction as the other modules in the chassis You can replace a power supply with another supported power supply that has the same power source type AC and the same wattage rating as...

Страница 47: ...assis Do not touch the electrical connections on the back side of the module and prevent anything else from coming into contact with and damaging the connectors Caution Step 2 Install the replacement power supply as follows a Holding the replacement power supply with one hand underneath the module and the other hand holding the handle turn the power supply so that its release latch is on the right...

Страница 48: ...y making sure that the power supply LED is green For information on what the power supply LEDs indicate see Power Supply LEDs on page 48 Cisco Nexus 9348GC FXP ACI Mode Hardware Installation Guide 38 Replacing Components Replacing an AC Power Supply ...

Страница 49: ...en racks If you are selecting an enclosed cabinet we recommend one of the thermally validated types either standard perforated or solid walled with a fan tray Note We do not recommend that you use racks that have obstructions such as power strips because the obstructions could impair access to field replaceable units FRUs Note General Requirements for Cabinets and Racks The cabinet or rack must al...

Страница 50: ...rack meets the following requirements The minimum vertical rack space per chassis must be one rack unit RU equal to 1 75 inches 4 4 cm The distance between the chassis air vents and any walls should be 2 5 inches 6 4 cm Requirements Specific to Perforated Cabinets A perforated cabinet has perforations in its front and rear doors and side walls Perforated cabinets must meet the following requiremen...

Страница 51: ...45 Environmental Specifications Specification Environment 32 to 104 F 0 to 40 C Ambient operating temperature Temperature 40 to 158 F 40 to 70 C Ambient non operating 8 to 80 with humidity gradation of 10 per hour 5 to 95 Operating Non operating Relative humidity 0 to 13 123 feet 0 to 4 000 meters Operating Altitude Switch Dimensions Height Depth Width Switch 1 72 inches 4 4 cm 1 RU With AC power ...

Страница 52: ... en us support interfaces modules transceiver modules products device support tables list html To see the transceiver specifications and installation information see https www cisco com c en us support interfaces modules transceiver modules products device support tables list html Switch Power Input Requirements The following table lists the typical amount of power consumed by the switch and it li...

Страница 53: ... 60 Hz Range 47 63 Hz AC input frequency 7 6 A at 100 VAC 3 65 A at 208 VAC Maximum AC input current 760 A at 100 VAC Maximum input volt amperes 350 W Maximum output power per power supply 33 A sub cycle duration Maximum inrush current 12 ms at 350 W Maximum hold up time 12 VDC Power supply output voltage 12 VDC Power supply standby voltage Climate Savers Platinum Efficiency 80Plus Platinum certif...

Страница 54: ... to the power supply and output power to the switch The BTU ratings are based on 36 VDC Power Cable Specifications The following sections specify the power cable that you should order and use with AC power supplies Power Cable Specifications for AC Power Supplies Cord Set Description Power Cord Part Number Locale Power Cord Jumper C13 C14 Connectors 6 6 feet 2 0 m CAB C13 C14 2M Power cord C13 to ...

Страница 55: ...lug 8 2 feet 2 5 m CAB 9K10A SW Switzerland 250 VAC 10 A BS1363 plug 13 A fuse 8 2 2 5 m CAB 9K10A UK United Kingdom No power cord included with switch NO POWER CORD All except Argentina Brazil and Japan Regulatory Standards Compliance Specifications The following table lists the regulatory standards compliance for the switch Table 1 Regulatory Standards Compliance Safety and EMC Description Speci...

Страница 56: ...000 3 2 EN61000 3 3 KN22 Class A CNS13438 Class A EMC Emissions EN55024 CISPR24 EN300386 KN 61000 4 series EMC Immunity The product is RoH 6 compliant with exceptions for leaded ball grid array BGA balls and lead press fit connectors RoHS Cisco Nexus 9348GC FXP ACI Mode Hardware Installation Guide 46 System Specifications System Specifications ...

Страница 57: ...witch is operational Green STS The switch is booting up Flashing amber Temperature exceeds minor alarm threshold Amber Temperature exceeds major alarm threshold Red The switch is not receiving power Off Fans and power supply modules are operational Green ENV At least one fan or power supply module is not operating Amber Port admin state is Enabled SFP is present and the interface is connected i e ...

Страница 58: ...he status for the module as shown in the following table Status LED LED Power supply is on and outputting power to the switch Off Green Power supply is connected to a power source but not outputting power to the switch power supply might not be installed in the chassis Off Flashing green Power supply is not receiving power Off Off Power supply warning possibly one of the following conditions High ...

Страница 59: ...e two post rack mount kit NXK ACC KIT 2P Quantity Description Illustration 1 Rack mount kit Bracket 2 M4 Phillips pan head screws 4 Number 8 Phillips flat head screws 8 Rack Mount Kit NXK ACC KIT 1RU The following table lists and illustrates the contents for the 1RU rack mount kit NXK ACC KIT 1RU Quantity Description Illustration 1 Rack mount kit Front brackets 2 Rear brackets 2 Slider rails 2 M4 ...

Страница 60: ...ing table lists and illustrates the contents for the accessory kit N3K C3064 ACC KIT Quantity Description Illustration 1 Rack mount kit Front mount angled bracket 2 Rear mount slider bracket 2 Slider rails 2 M4 x 7 mm mounting screws 16 1 Console cable with DB 9F and RJ 45F connectors 1 kit Ground lug kit Two hole lug 1 M4 x 8 mm Phillips pan head screws 2 1 EAC Compliance document Not applicable ...

Страница 61: ...L https www cisco com warp public 687 Directory DirTAC shtml If you purchased this product through a Cisco reseller you might receive additional contents in your kit such as documentation hardware and power cables Note For a list of the available power cables see Power Cable Specifications on page 44 Cisco Nexus 9348GC FXP ACI Mode Hardware Installation Guide 51 Additional Kits Additional Kits ...

Страница 62: ...Cisco Nexus 9348GC FXP ACI Mode Hardware Installation Guide 52 Additional Kits Additional Kits ...

Страница 63: ...tion and accessibility The following table lists the site planning tasks that we recommend that you complete before you install the switch Your completion of each task ensures a successful switch installation Verification Time and Date Planning Activity Space evaluation Space and layout Floor covering Impact and vibration Lighting Physical access Maintenance access Environmental evaluation Ambient...

Страница 64: ...center ground Cable and interface equipment evaluation Cable type Connector type Cable distance limitations Interface equipment transceivers EMI evaluation Distance limitations for signaling Site wiring RFI levels Contact and Site Information Use the following worksheet to record contact and site information for the installation Contact person Contact phone Cisco Nexus 9348GC FXP ACI Mode Hardware...

Страница 65: ...ial number Product number Use the following worksheet to record network related information Switch IP address Switch IP netmask Hostname Domain name IP broadcast address Gateway router address DNS address Use the following worksheet to record information about the modules in the switch Notes Module Serial Number Module Type Module Slot Fan module 1 Cisco Nexus 9348GC FXP ACI Mode Hardware Installa...

Страница 66: ...r Module Type Module Slot Fan module 2 Fan module 3 Power Supply 1 Power Supply 2 Cisco Nexus 9348GC FXP ACI Mode Hardware Installation Guide 56 Site Preparation and Maintenance Records Site Preparation and Maintenance Records ...