Cisco Nexus 3000 Series Hardware Installation Guide
OL-25338-04
Chapter 1 Overview of the Cisco Nexus 3000 Series Switches
Cisco Nexus 3016 Switch
Power Supply for the Cisco Nexus 3016 Switch
The Cisco Nexus 3000 Series switch has two slots for power supplies that are initially installed with one
or two AC or DC power supplies that have forward or reverse airflow for their cooling. The switch
requires only one power supply for its operations, but you can include a second one for redundancy.
To determine which part number to use when ordering replacement power supplies, see
Table 1-2
.
If the chassis has two power supplies, you can hot swap one of the power supplies during operations. If
the chassis has only one power supply, you can install the new power supply in the open slot, turn on that
power supply, and then remove the original power supply during operations.
Caution
You can order replacement power supplies with forward airflow or reverse airflow. Be sure to order the
same direction of airflow as is used with the switch. If there is a black stripe across the front of the fan
trays and power supplies, the switch is running reverse airflow and you must order power supplies with
reverse airflow (each module has a black stripe). If there is no black stripe across the front of these
modules, the switch is running forward airflow and you must order replacement modules with forward
airflow (modules that do not have a black stripe).
Caution
The switch must run with all of its power supply and fan tray modules taking in air from a cold aisle and
exhausting air to the hot aisle. If they take in air from a hot aisle, an overtemperature condition can occur
and the switch will shut down. If the airflow directions are mixed in the same switch, you will see an
error.
Note
Never leave a power supply slot empty. If you remove a power supply, replace it with another one. If you
do not have a replacement power supply, leave the non functioning one in place until you can replace it
or fill the slot with a filler blank module (part number N2200-P-BLNK).
For power supply specifications, see the
“Power Specifications” section on page B-2
. For information
about the power supply LEDs and what they indicate, see the
“Power Supply Status” section on
page D-3
.
Table 1-2
Cisco Nexus 3016 Power Supply Part Numbers
Power Source
Airflow Direction
Power Supply Part Number
AC
Forward
N2200-PAC-400W=
AC
Reverse
N2200-PAC-400W-B=
DC
Forward
N2200-PDC-400W=
DC
Reverse
N3K-PDC-350W-B=