8
Getting Started and Product Document of Compliance for the Cisco Catalyst IW6300 Heavy Duty Series Access Points
Connecting AC Power to IW-6300H-AC-x–K9
Connecting AC Power to IW-6300H-AC-x–K9
Note:
When you install the conduit, be sure to comply with the local electrical codes for your area.
To route and connect the ground and AC power cabling to the IW-6300H-AC-x-K9 access point model:
1.
Loosen captive bolts (
1
) with 1/2” or 13-mm socket and open the access point cover.
2.
Fold the access point cover back.
Notes
The installer/integrator is
responsible for supplying the
appropriate certified components
as part of the overall designed
system and must maintain the
access point environmental
integrity of IP66/67 rating.
The water-tight gland device
selected by the
installer/integrator must be equal
to or greater (better) than the
specifications listed for the
device.
1—Customer-supplied harness
2—Customer-supplied cable (ATEX/IECEx only)
3—Terminal block
3.
Route the AC power cable through the 1/2” NPT port.
4.
Use a wire stripper tool to remove the insulation from each 18 AWG (0.75mm
2
) wire. Remove only enough wire
to provide a solid connection in the terminal block and the internal ground. The hot wires should have no bare
wire exposed after the connection is made.
5.
Insert ground wire into the internal ground.
6.
Insert each hot wire into the AC entry terminal block.
7.
Use a Phillips screwdriver to tighten the terminal block set screws to secure the wires in the terminal block.
8.
Verify that no bare wire is exposed. If wire is exposed, remove it from the terminal block, adjust the length, and
reinstall.
9.
Close the access point cover.