Connecting to DC Power and CAN Bus Wiring

This product relies on the building’s installation for short-circuit (overcurrent) protection. Ensure that the
protective device is rated not greater than 60 VDC minimum, 5A maximum.

Statement 1005

Warning

Connect the unit only to DC power source that complies with the safety extra-low voltage (SELV) requirements
in IEC 60950 and IEC 62368 based safety standards.

Statement 1033

Warning

This product requires short-circuit (overcurrent) protection, to be provided as part of the building installation.
Install only in accordance with national and local wiring regulations.

Statement 1045

Warning

When you connect or disconnect the power and/or alarm connector with power applied, an electrical arc can
occur. This could cause an explosion in hazardous area installations. Be sure that all power is removed from
the switch and any other circuits. Be sure that power cannot be accidentally turned on or verify that the area
is nonhazardous before proceeding.

Statement 1058

Warning

Explosion Hazard—The area must be known to be nonhazardous before installing, servicing, or replacing the
unit.

Statement 1082

Warning

Explosion Hazard—Substitution of components may impair suitability for Class I, Division 2/Zone 2.

Statement

1083

Warning

Plugs and Pinouts

The IR1800 uses a DC power accessory kit (part number PWR-MF4-125W-AC). This needs to be ordered
separately. The power entry receptacle is on the IR1800. The pinouts are shown in the following figure.

Connecting the Router

3

Connecting the Router

Connecting to DC Power and CAN Bus Wiring

Содержание Catalyst IR1800 Rugged Series

Страница 1: ... devices install the router according to the instructions in Installing the Router Preventing Damage to the Router To prevent damage to your router turn off the power to the devices and to the router until all connections are completed For hazardous location environments follow these warnings when connecting to destination ports antenna serial Ethernet and console ports If you connect or disconnec...

Страница 2: ...nstalled in the PC server or workstation Step 3 Optional Connect additional servers PCs or workstations to the other Ethernet switch ports Connecting a PC to the Console Port Connect a PC to the console port either to configure the software by using the CLI or to troubleshoot problems with the router To connect a terminal or PC to the console port on the router and access the CLI follow these step...

Страница 3: ...rm connector with power applied an electrical arc can occur This could cause an explosion in hazardous area installations Be sure that all power is removed from the switch and any other circuits Be sure that power cannot be accidentally turned on or verify that the area is nonhazardous before proceeding Statement 1058 Warning Explosion Hazard The area must be known to be nonhazardous before instal...

Страница 4: ...erential Signal CAN_N 4 The IR1800 can be installed without connecting to the CAN Bus There is a 2 wire cable that can be ordered CAB PWR 15 MF4 The following is a diagram of the cable Verifying Connections To verify that all the devices are properly connected to the router turn on all the connected devices and then check the LEDs Connecting the Router 4 Connecting the Router Verifying Connections...

Отзывы: