It is not required to place the chassis power switch in the Standby position if you want to hot-swap
a single power supply.
Note
Step 2
Unplug the power cable from the power supply.
Step 3
Press the retaining latch towards the pull handle, grasp the handle with one hand, and pull the power supply
out of the slot while supporting the weight of the power supply with the other hand.
Step 4
Repeat these steps if it is required to remove the other AC power supply.
Installing AC Power Supplies
Do not install the power supplies with the chassis cover off.
Note
Procedure
Step 1
Ensure that the chassis power switch on the chassis is in the Standby position.
It is not required to place the chassis power switch in the Standby position if you want to hot-swap
a single power supply.
Note
Step 2
Insert the power supply module into the appropriate slot(s), making sure that the retention latch is firmly
placed. You can verify that the power supply module is firmly latched by gently pulling the power supply
handle.
Step 3
Insert the power supply cables firmly into the power supplies.
Ensure that both power supplies are inserted firmly and the power cords are in place.
Note
Step 4
If you have changed the chassis power switch to the Standby position in Step 1, press the power switch to the
On position.
The power supply LEDs are illuminated (green).
Removing DC Input Power Supplies
The DC power supply has a terminal block that is installed into the power supply terminal block header.
Procedure
Step 1
Turn off the circuit breaker from the power source.
Step 2
Ensure that the chassis power switch is in the Standby position.
Removing and Replacing FRUs
5
Removing and Replacing FRUs
Installing AC Power Supplies