
34
Figure 5
Attaching the Bracket to the DIN Rail
1.
Position the router so that the spring of the Din clip (
1
) rest on the Din rail (
2
).
2.
Push up the router so that the spring of the Din clip (
1
) compresses and the top hook of the Din clip (
3
) slides and
clamps to the Din rail (
2
).
3.
To remove the router from the DIN Rail, simply reverse the procedure.
NOTE:
The procedure to attach the unit to the rail is the same with both orientations.
Installing the Router Ground Connection
The router must be connected to a reliable earth ground. Install the ground wire in accordance with local electrical safety
standards.
For NEC-compliant grounding, use size 14 AWG (1.6mm) or larger copper wire and a ring terminal with an inner
diameter of 1/4 in. (5 to 7 mm).
For EN/IEC 60950-1 compliant grounding, use size 18 AWG (1.02mm) or larger copper wire.
WARNING:
This equipment must be grounded. Never defeat the ground conductor or operate the equipment in the
absence of a suitably installed ground conductor. Contact the appropriate electrical inspection authority or an electrician
if you are uncertain that suitable grounding is available. Statement 1024
NOTE
: Depending on the kit shipped with your router, the grounding lug may have one hole or two holes.
CAUTION:
Cable distribution system should be grounded (earthed) in accordance with ANSI/NFPA 70, the National
Electrical Code (NEC), in particular Section 820.93, Grounding of Outer Conductive Shield of a Coaxial Cable.
Содержание 807
Страница 38: ...36 ...