A-3
Cisco 12010, Cisco 12410, and Cisco 12810 Router Installation and Configuration Guide
OL-11496-01
Appendix A Technical Specifications
Router Specifications
Caution
To ensure that the chassis configuration complies with the required power
budgets, use the on-line power calculator. Failure to properly verify the
configuration may result in an unpredictable state if one of the power units fails.
Contact your local sales representative for assistance.
Table A-2
AC Electrical Specifications
Description
Value
Power
2791 VA (volt-amps) per AC power supply
(2 AC power supplies per system)—original
series
3000 VA (volt-amps) per AC power supply
(2 AC power supplies per system)—original
series
Rated input voltage
1
1.
For each AC power supply module.
200–240 VAC nominal (range: 180 to 264 VAC)
220–240 VAC (UK)
Rated input line frequency
1
50/60 Hz nominal (range: 47 to 63 Hz)
50/60 Hz UK
Input current rating
1
15 A maximum @ 200 VAC
13 A maximum @220 to 240 VRMS (UK)
Source AC service
requirement
1
20 A North America; 16 A international;
13 A UK
Heat dissipation
(total maximum)
2800 W@9,544 BTU/hour
Redundancy
2 AC power supply modules required for 2N
redundancy