Chapter 3 Installing the Router
Connecting GRP Route Processor Cables
3-42
Cisco 12010, Cisco 12410, and Cisco 12810 Router Installation and Configuration Guide
OL-11496-01
Note
To comply with Telcordia GR-1089 NEBS standard for electromagnetic
compatibility and safety, connect all console, auxiliary, and Ethernet interfaces
only to intrabuilding or nonexposed wiring or cabling. The intrabuilding cable
must be shielded and the shield must be grounded at both ends.
Connecting to the GRP Console Port
The system console port on the GRP is an EIA/TIA-232 DCE DB-25 receptacle
for connecting a data terminal to perform the initial configuration of the router.
The console port requires a straight-through RJ-45 cable.
See the
“GRP Auxiliary and Console Port Connections” section on page 2-23
additional information about the GRP console port.
Use the following procedure to connect a data terminal to the GRP console port.
Step 1
Set your terminal to these operational values: 9600 bps, 8 data bits, no parity,
2 stop bits (9600 8N2).
Step 2
Power off the data terminal.
Step 3
Attach the terminal end of the cable to the interface port on the data terminal.
Step 4
Attach the other end of the cable to the GRP console port.
Step 5
Power on the data terminal.