![Circutor SVGm Скачать руководство пользователя страница 69](http://html1.mh-extra.com/html/circutor/svgm/svgm_instruction-manual_2608356069.webp)
69
Instruction Manual
SVGm
Figure 69: Configuration screen: Time Programmer: cos
Φ
�
Select the Scheduling Mode from the drop-down menu:
●
Mode 1
In this mode,
cos
Φ
is set to a fixed value. The device will attempt to ensure that the reactive power on
the mains side corresponds to the specified
cos
Φ
.
Table 31: Configuration values: Mode 1�
Mode 1
cos
Φ
Offset
Range of values
0.7 ... -0.7
0 ... 10000 kvar.
●
Mode 2
In this mode, two limits are defined to form an acceptance range. The device will adjust the reactive
power on the mains side to keep
cos
Φ
within the specified acceptance range.
This mode minimises the amount of power used by the device to compensate for reactive power, thus
reducing its energy consumption.
Table 32: Configuration values: Mode 2�
Mode 2
cos
Φ
Offset
Range of values
0.7 ... -0.7
0 ... 10000 kvar.
●
Fixed Q
This way, the device generates a constant reactive power.
Table 33: Configuration values:Fxed Q�
Fixed Q
Minimum value
0 kvar
Maximum value
10000 kvar
●
Off
If this mode is programmed, the device turns off during the scheduled time band.
Press the
key to access the next configuration step
Press the
key to access the main screen of the device without saving the configuration values.
Содержание SVGm
Страница 1: ...SVGm M248B01 03 22A Static var generator INSTRUCTION MANUAL ...
Страница 2: ...2 SVGm Instruction Manual ...
Страница 105: ...105 Instruction Manual SVGm 14 CE CERTIFICATE ...
Страница 106: ...106 SVGm Instruction Manual ...
Страница 107: ...107 Instruction Manual SVGm ...