Code
Type
Sensivity (A)
Tripping delay (s)
Communications
P24652
RGU - 10C MT
0,03-0,1-0,3-0,5-1-3
by direct adjustment
5-10-30 by
SETUP
INS-SEL-0,02-0,1-0,2-0,3-0,4-0,5-0,75-1
by direct adjustment
3-5-10 by
SETUP
Available
RS-485
P 2 X X X X 0 0 X
Código
Code
Código interno
Internal code
Tensión de
alimentación
Power supply
230 V a.c.
110 V a.c.
0
1
RGU-10C MT Electronic earth leakage protection relay with self-reclosing system
For instance, RGU-10C MT supplied by 110 V a.c.
GENERAL DESCRIPTION
DESCRIPTION LED AND BUTTONS.
- Device with programmable differential relay with self-reclosing system. Symbol
in LCD.
- It has 2 independents outputs by relays. Trip and locked by reclosing.
- It has 1 input for external Trip/Reclose. This input is not opto - coupled.
- Mounting in Rail DIN 46277 (EN 50022) or panel 72x72 by mean accessory (M5ZZF1)
- Associated to a
/
Series external , toroidal current transformer.
- It must be asociated to a MCB motorized with or without a trip coil.
- It verifies connection with differential transformer
by means inductive test.
- Leakage detection and measurement is via calculating its true efective value (TRMS).
- Display settings values and instant residual current to its accociated units.
- Shows equipment status via a display and 2 LED.
- 5 button equipment setup and setting.
- 2 button equipment TEST and RESET.
WG WGS
WG/WGS
-
INDICATION BY LED AND DISPLAY.
RECLOSING THE EQUIPMENT.
RELAY PARAMETERS SETTING
-
-
LED and display signals a change
of status by changing from green to red.l
Display event type messages or values.
The yellow LED is blinking. Red Display shows the
tripp cause fluctuating with partial reclosures No
.
The yellow LED is fixed. The equipment arrives al
maximun number of reclosures established by the
self-reclosing sequence. Red display shows the cause.
-
By short press on
the display shows the number of reclosures by
earth leakage, short ciruit-overload faults and total number. The partial number are floating pages
In these pages it can configure the self-reclosing sequence by press
button.
- BY
/
1. Automathic (earth leakage, short ciruit-overload faults or manual).
Enabled.
2. Manual reclose by pushing button
3. External reclose sytem by remote or communications signal. When it forces a trip by remote
signal, only it can reclose by another remote signal.
4. Manual reclose circuit breaker associated.
In the case 2 and 3 the all partial counters of reclosures returns to a zero.
, .
t
.
SAVE.
.
. .
. Select the default position of the relay contacts
7-8-9 that indicates the situation of locked by reclosures of the device . In (Std) 8-7 NA / 8-9 NC
and (+) 8-7 NC / 8-9 NA and appears the
symbol in display.
. In reclosure partial numbers by press
button we
configure the self-reclosing sequence referred at the page which it’s showing us. By default is
configured nº10 by earth leakage protection and nº5 by short-circuit/overload protection.
TRIP RELAY.
BETWEN RECLOSURES.
LOCKED BY RECLOSURES
No OF RECLOSURES.
PROG
REC
TRIP LOCKED BY RECLOSURES
RESET
-
-
,
- SIGNALLING CONTACTS RELAY STATE, std/+
- SELF-RECLOSING SYSTEM, REC
REC
( ,
y std/+ )
t I
d
d
t
I
I
d
d
d
d
SETTING TRIP DELAY
SENSITIVITY SETTING
The
message and two values appear on the screen after
pressing the
button. The lowest value indicates the current set value and the highest is the
values to be configured which are displayed by pressing
The selected value to be saved is
displayed by showing the message
The same operation as above setting is carried out by pressing
Tripping cause
Message display
Test
Remote signal trip/reclose
Earth leakage fault
Short circuit / Overload fault
Communications
TESt
EXT
DIF / valor
MAG
REM
PROG
+
Others MESSAGES by display
SAVE
EXIT
OVR
ERRt
Enter setting values
Exits setting mode
Value reading off scale
Poor toroidal conection
M98205901-03-09B
P24652001
PARAMETERS BY
DIRECT ADJUSTMENT
-DELAY SETTING
-
ROTATION
SETUP
-SENSIVITY SETTING
-CONTACTS SETTING NO/NC
-ENABLE/DISABLE
SELF-RECLOSING SYSTEM
REC
SREC
No RECLOSURES
TIME SEQUENCES
RESET TIME
RECLOSE SEQUENCES BY EARTH LEAKAGE CURRENT FAULT
SREC No RECLOSURES
TIME SEQUENCE
RESET TIME
RECLOSE SEQUENCE BY SHORTCIRCUIT/OVERLOAD FAULT
TECHNICAL FEATURES
Relay type: Electronic class A. High frequency current filtering.
- Reclosing type: Authomatic, RESET button or by cutting power supply.
- Rated power supply voltage
Operating temperature
Connections
Permissible cable section:
Recommended tightening torque: 0.5-0.6 Nm
Length of cable to strip:
7 mm
Switch Output contact features
Rated current/Maximum instant current
Rated voltage/Maximum switching voltage
Rated load in
- Tipo
: 230 o 110 Va.c. (+/- 20%) 50/60 Hz, 6 VA
-
: -10ºC / 50ºC
-
:
0,127 - 2,082 mm
-
13-14-15, 7-8-9 and 5-6
: 6/10 A a.c.
: 250/230 V a.c.
AC: 2,500 V·A
Contacts protected by varistor
- Varistor Features
Maximun Voltage: 275 Va.c.
-Characteristics input remote Trip/Reclose 1-2
Input not using optocoupler
2
REC
REC
MT
REC
MT
REC
WARNING: The reclosing sequences marked by
is recommended for motorized circuit breakers with or
without trip coil. I >63 A.
N
Maximun DC Load Breaking
Capacity:
Maximun opening current
Electrical useful life for AC
loads: No of cycles
MAG
¡ IMPORTANT
!
The relay only self-recloses before a trip by earth leakage, short-circuit/overload current fault. The Test (red button) only
verifies the relay trips the protection. It recloses only by manual pressing RESET button.
0
DISABLED
1
2
1 minute
30 minutes
2
2
1 minute
60 minutes
3
2
90 s
30 minutes
4
2
90 s
60 minutes
2
3 minutes
30 minutes
6
...
...
...
7
...
...
...
8
...
...
...
5
0
DISABLED
1
6
8, 16, 30, 59, 115 and 224 s
15 minutes
2
30
20, 40 s and 5 min. to the end
15 minutes
3
8
30 s, 1, 2, 3, 4, 5, 6 and 7 min
15 minutes
4
6
10, 20, 30, 60, 130 and 600 s
15 minutes
5
6
2, 4 and 8 min. to the end
15 minutes
6
7
30 s, 1, 2, 3, 4, 8 and 16 min.
30 minutes
7
10
1 min.
30 minutes
8
10
90 s
30 minutes
9
8
2, 4 and 6 minutes to the rest
15 minutes
10
3 minutes
30 minutes
11
7
2, 4, 8, 16, 32, 32 and 32 minutes
15 minutes
10
12
31
2, 4 and 6
15 minutes
13
6
8 s
15 minutes
14
...
...
...
minutes to the rest
MAG
MAG
MAG
MAG
MAG
MAG
MAG
REC
REC
GREEN LED: ON
RED LED: TRIPPED BY FAULT
SCREENS /
SETUP
R
RESET button: It reinitiates the operation of the equipment by any event
that tripps it.evento. It indicates the equipment version.
YELLOW LED: Locked by reclosures (fix)
Betwen reclosures (blinking)
Button
FREQ
LIM
SEC.T
TRIP
Button
60 Hz
10 s, 30 A
RST.C
Mb
Pulsador
PROG
PERIPHERICS
BAUDS
PARITY
COM
PsI
1 ..
.. 99
2.4
4.8
9.6
19.2
38.4
57.6
115.0
0
EN
OD
50 Hz
1 s, 3 A
St
MA
-
, PER( ) / BD(
) / PAR( ), communications.
-
, (
) frecuency (Hz)
-
,(
), range of values (Id / td)
-
, (
),contacts 5-6 [
-
, (
), initiates the partials counters.
COM
FREQ
LIM
SEC. T
RST.C
NA/NC]
-
(without trip coil)
TRIP, (
), breaking element
1
9.6
0
50
1s, 3A
NO
NO
MA
Default values in
SETUP
TEST button: It makes a forced firing to verify the protection.
YES
NO
SETUP
SETTINGS
A long press in
activates the
settings. In this operating
mode by pressing buttons
and
it shows the submenus and the
setting values to modify . With
these
SETUP
PROG
PROG
PROG
new setting values are
validated, the message
is shown by display and exits setting
mode. In case of keypad inactive, it exits setting mode and the message
is shown by display wihtout changes.
In
(Circuit Breaker), The value
is used when the CB don
’
t need a
trip coil. The value
is used when CB needs one.
In
it defines the working mode of outputs contacts relay 5-6. By
default 5-6 is normally open (St )
SAVE
EXIT
TRIP
SEC.T
(LOCKED SIGNAL)
(See graph)
(See graph)