To change the scales, press the
td
key repeatedly.
Programming values:
10s - 30 A
or
1s - 3 A�
When the desired value is shown on the screen, validate the number by pressing the
PROG
key. The
device exits the programming menu, and shows a screen with the
“SAVE”
message.
6�2�3�- CIRCUIT BREAKER
The display shows
TRIP�
To change the value, press the
PROG
key. The display shows the
current circuit
breaker.
To change the
circuit breaker, press the
td
key repeatedly.
Programming values:
Mb
(coil trip)
or
Ma (magnetothermic trip)�
When the desired value is shown on the screen, validate the number by pressing the
PROG
key. The
device exits the programming menu, and shows a screen with the
“SAVE”
message.
6�2�4�- RESETTING THE PARTIAL METER
The display shows
RST�C
. To change the value, press the
PROG
key. The screen shows the option to
reset the meter or not.
To switch between the alternatives, press the
td
key repeatedly.
Programming values:
YES
or
NO�
When the desired value is shown on the screen, validate the number by pressing the
PROG
key. The