Response:
Address
Function
Initial
Register
Relay action
CRC
01
05
0000
FF00
8C3A
6.3.- MODBUS COMMANDS
6�3�1�- MEASUREMENT VARIABLES AND DEVICE STATUS
All the addresses of Modbus memory are in Hexadecimal.
For these variables is implemented the
Function 0x03
and
0x04
.
Table 7: Modbus memory map (Table 1)
Parameter
Format
Address
Units
Current
float
12
A
Current
int
10C
0.001 A
Frequency
float
2C
Hz
Frequency
int
120
0.01 Hz
Table 8: Modbus memory map (Table 2)
Parameter
Format
Address
Value
Status of output relays bit [0] - bit [2]
bit [32]
100 - 101
0:
open
1:
closed
Status of digital inputs bit [0] - bit [2]
bit [32]
102 - 103
0:
open
1:
closed
Communications ID
int
104
504
6�3�2�- OUTPUT RELAYS
All the addresses of Modbus memory are in Hexadecimal.
For these variables is implemented the
Function
0x01, 0x05
and
0x0F�
Table 9: Modbus memory map (Table 3)
Parameter
Format
Address
Value
Output relay 1
bit
0000
0:
open
, 1:
closed
Output relay 2
bit
0000
0:
open
, 1:
closed
6�3�3�- DIGITAL INPUTS
All the addresses of Modbus memory are in Hexadecimal.
For these variables is implemented the
Function
0x02�
Table 10: Modbus memory map (Table 4)
Parameter
Format
Address
Value
Digital input 1
bit
0000
0:
open
, 1:
closed
Digital input 2
bit
0000
0:
open
, 1:
closed
34
DHC-96 Aac
Instruction Manual
Содержание DHC-96 Aac
Страница 1: ...INSTRUCTION MANUAL M226B01 03 19A AC Ammeter DHC 96 Aac...
Страница 2: ...2 DHC 96 Aac Instruction Manual...
Страница 39: ...49 8 68 5 81 2 96 10 max Figure 22 Dimensions of the DHC 96 39 Instruction Manual DHC 96 Aac...
Страница 41: ...10 CE CERTIFICATE 41 Instruction Manual DHC 96 Aac...
Страница 42: ...42 DHC 96 Aac Instruction Manual...
Страница 43: ...43 Instruction Manual DHC 96 Aac...
Страница 45: ...45 Instruction Manual DHC 96 Aac...