5�1�- PLUG&PLAY
The Plug&Play function assists the user during the configuration of the unit, since it automatically
configures the basic parameters that are required for the unit to perform its regulation functions
correctly.
To start the Plug&Play process, press the
.
The process enters editing mode. It is identified by the
symbol and the blinking of the digits of
the display.
Press the
key to switch from
OFF
to
START
Press the
key to start the Plug&Play function. Once started, the unit undertakes a process of
connecting and disconnecting capacitors, measurement and calculation in order to obtain the following
parameters of the capacitor bank:
Connection type,
Phase,
Number of steps.
Program
C/K factor,
These parameters can also be configured manually from their respective screens.
When the Plug&Play process of the unit is active, this screen is displayed with the
symbol
blinking (it may take several minutes).
The capacitors are connected and disconnected during the process and this will be displayed on the
screen.