POWER FACTOR REGULATOR Computer
max
6f /
max
12f
The
Computer
max
6f
/
max
12f
PF regulators measure cos
in a supply system and control the connection and disconnection of capacitors
to obtain a target programmed value.
This manual is an easy guide for the use and operation of the
Computer
max
6f
/
max
12f
. For more information, the complete
manual can be downloaded from the web site of Circutor:
www.circutor.es
Any manipulation or use of the equipment out of the conditions
specified by the manufacturer may put in risk the user safety
. Before
any maintenance operation the equipment must be disconnected from power
supply. In case of miss operation or protection fault the equipment must be
disconnected from supply and remain out of service ensuring against any
accidental reconnection.
1.- Regulator Connection
For proper operation it’s necessary to install a current transformer, CT
(normally In / 5 A), which primary must be sized according to the
maximum expected load current in the installation.
The regulator supply (C-D terminals) must be taken between two
phases and the CT should be located in the third phase. See technical
characteristics for cable sizes and required protections.
Must use an switch or automatic switch for supply the regulator
The current transformer , CT,
must be located so that it
measures the whole load current
plus the correction capacitors
2.- Technical Characteristics
Supply and V measurement input
terminals (C-D)
480,400, 230 or 110 VAC +15% -10% ; 45-65 Hz , (see label)
Connect preferably to phases L2-L3
Supply cables size and protection Cross section 1,5mm
2
; 0,5 to 2A Fuses gl type
Current measurement circuit
Current transformer (CT) , In /5 , Place preferably in phase L1
Minimum cabling cross section 2,5mm
2
Current measurement margin
0,05 to 5 A (maximum ov20%)
Accuracy of measurements
Voltage and current :1%; cos
: 2%
1 dígit
Max. Power consumptions
110V: 7,3 VA 230V: 7,5 VA 400V: 5 VA 480V: 7 VA
Display
1 line x 3 digits x 7se 20 icons
Output Contacts
MOS static output. Max 24V, 0.15A
Alarm Output
Last output automatically set as alarm output , if not in use
Compliant to the following
Standards
EN 61010, EN 61000-3-2, EN 61000-3-3, EN 50081-2, EN 50082-
1, EN 50082-2, EN 61000-4-2, EN 61000-4-4, EN 61000-4-8, EN
61000-4-5, EN 61000-4-11 , UL 94
Safety / Insulation
Category III , Class II, According to EN 61010-1,
Environment limit conditions
Temperature limits: -20ºC a +60ºC; Relative Humidity 95%
(without condensation). Max. Altitude: 2000m
Protection degree
IP40 (panel mounted)
IP30 (regulator box) , According to EN-60529
Control system
FCP (Minimum number of operations)
Total (Connection/Disconnection of all stages needed)
3.- Four Quadrants Operation
The
Computer
max
6f
/
max
12f
regulators operate in 4 quadrants (suitable
for imported or exported active power). For exported power, a negative
symbol is displayed in the cos
indication. Check phase connection and
setup if there is no exported energy and the indication is not correct (see 4.3,
SET-UP - phase)
Display / Teclado
Standard mode: Displays cos
cos
Indication / setting
C/K setting. See paragraph 6
Program setting. See 4.2
Delay time setting for switching on/off operations
Nr of steps setting
Setting CT phase and polarity connection
- Cursor keys (when in setting mode)
- Manual ON / OFF (push during more than 1s when in RUN mode)
- Push both to see the Nr of connected steps
SETUP KEY: Push during more than 1s to enter SETUP mode
Lagging current indication (Inductive load)
11
Leading current indication (Capacitive load)