9.2 Gas operation
CAUSE
TROUBLE
THE BURNER
DOES
N’TSTART
CONTIN
UE
WITH P
R
E
-
PURGE
DOES
N’T
S
T
A
R
T
AND LOCK
-
OUT
DOES
N’T S
T
A
R
T
AND
REPE
ATS THE
CY
CLE
STARTS AND REPE
ATS THE
CYCLE
STARTS AND LOCK
-OUT
THE FL
AME MONI
TOR
DEVICE DOES
N’T
GI
VE
C
O
NSENT TO
S
T
ART
DOES
EN’T S
W
ITCH TO
H
IGH
FLAME
DOES
EN’T R
E
TUR
N
IN
LOW
FLAME
LOC
K
-OUT DU
RING
OP
ERATI
O
N
TURN
S
O
F
F AND REPE
ATS
CYCLE
DURING OPERA
T
ION
MAIN SWITCH OPEN
z
LACK OF GAS
z
z
MAXIMUM GAS PRESSURE SWITCH DEFECTIVE
z
z
THERMOSTATS/PRESSURE SWITCHES DEFECTIVES
z
z
z
OVERLOAD TRIPPED INTERVENTION
z
AUXILIARIES FUSE INTERRUPTED
z
DEFECTIVE CONTROL BOX
z
z
z
z
z
DEFECTIVE ACTUATOR
z
z
z
AIR PRESSURE SWITCH FAULT OR BAD SETTING
z
z
z
z
MINIMUM GAS PRESSURE SWITCH DEFECTIVE OR GAS
FILTER DIRTY
z
z
z
z
z
IGNITION TRANSFORMER FAULT
z
IGNITION ELECTRODES BAD POSITION
z
BUTTERFLY VALVE BAD SETTING
z
z
DEFECTIVE GAS GOVERNOR
z
z
z
z
GAS VALVE DEFECTIVE
z
BAD CONNECTION OR DEFECTIVE HIGH/LOW FLAME
THERMOSTAT OR PRESSURE SWITCH
z
z
ACTUATOR CAM WRONG SETTING
z
z
z
UV PROBE DIRTY OR DEFECTIVE
z
z
z