EN-83
EREBA He
7 - PARAMETERS OVERVIEW
7.1 - Parameters list
This section includes an overview of all parameters that can be read or modified by the user.
The parameters are sorted as follows:
●
001 to 299
Display parameters
●
301 to 399
Maintenance parameters
●
401 to 499
Setpoint parameters
●
501 to 799
Configuration parameters
Legend:
No
No access
RO
Read-Only
RW
Read/Write
RO/d
Read-Only and Display on the WUI
RO/F
Read-Only and Parameter Forcing by CCN
Par.
CIAT
Jbus
Mnemonic
Description
Range
Default
Unit
WUI
Table
001
4E54H
OAT
Outdoor Air Temperature
1/10°C
RO/d
RO/F
GENUNIT
002
4E7CH
IAT
Indoor Air Temperature
1/10°C
RO/d
RO/F
GENUNIT
003
4E50H
EWT
Entering Water Temperature
1/10°C
RO
RO/F
GENUNIT
004
4E52H
LWT
Leaving Water Temperature
1/10°C
RO
RO/F
GENUNIT
005
TR
Refrigerant Temperature
1/10°C
RO
RO/F
GENUNIT
006
SPARE_T
Spare Temperature
1/10°C
RO
RO/F
GENUNIT
007
roomtemp
Room Temperature
1/10°C
RO
RO/F
GENUNIT
008
4E5AH
sst
Saturated Suction Temp
1/10°C
RO
RO
GENUNIT
009
4E64H
ts
Suction Temperature
1/10°C
RO
RO
GENUNIT
010
4E74H
td
Discharge Temperature
1/10°C
RO
RO
GENUNIT
011
te
Lower Air Exchanger Temp
1/10°C
RO
RO
GENUNIT
012
tl
Upper Air Exchanger Temp
1/10°C
RO
RO
GENUNIT
013
to
Inv. Outdoor Air Temp
1/10°C
RO
RO
GENUNIT
014
th
Heatsink Temperature
1/10°C
RO
RO
GENUNIT
015
4E68H
sh
Superheat Temperature
1/10 K
RO
RO
GENUNIT
016
510CH
sh_targ
Superheat Target Temp
1/10 K
RO
RO
GENUNIT
017
dc_volt
Inverter DC High Voltage
V
RO
RO
GENUNIT
018
hv_stat
HV Bus Comm. Status
0/1 [Normal/Alarm]
-
RO
RO
GENUNIT
019
inv_mod
Inverter Current Mode
-
RO
RO
GENUNIT
020
freq_min
Actual Min Compr. Freq
1/10 Hz
RO
RO
GENUNIT
021
freq_max
Actual Max Compr. Freq
1/10 Hz
RO
RO
GENUNIT
022
4ED6H
FREQ_REQ
Requested Compr. Freq
1/10 Hz
RO
RO/F
GENUNIT
023
freq_cur
Actual Compressor Freq
1/10 Hz
RO
RO
GENUNIT
024
4EC0H
pmv_pos
PMV Position
0 to 500
step
RO
RO
GENUNIT
027
4EE6H
upr_fan
Upper Fan Speed
0 to 1000
rpm
RO
RO
GENUNIT
028
4EEEH
lwr_fan
Lower Fan Speed
0 to 1000
rpm
RO
RO
GENUNIT
029
4ECEH
EXCH_HTR
Exchanger Heater
0/1 [Off/On]
-
RO
RO/F
GENUNIT
030
4ED0H
BOILER
Boiler Output
0/1 [Off/On]
-
RO
RO/F
GENUNIT
031
4ED2H
EHS
Electrical Heat Stages
0 to 3
-
RO
RO/F
GENUNIT
035
SPARE_P
Spare Pressure
KPa
RO
RO/F
GENUNIT
039
(1)
to2
Corrected Inverter TO
1/10°C
RO
RO
GENUNIT
041
9C44H
4E24H
CHIL_OCC
Occupancy Mode
0 to 2
-
RW/d
RW/F
STATUS
Away/
Sleep/
Home]
042
sum_mode
Summer Mode
0/1 [No/Yes]
-
RO
RO
STATUS
043
nightmod
Night Mode
0/1 [No/Yes]
-
RO
RO
STATUS
044
MOD_REQ
System Mode Request
0 to 9
-
RW/d
RW/F
STATUS
045
MOD_STAT
System Mode Status
0 to 109
-
RO/d
RO
STATUS
047
mod_ovr
System Mode Override
0 to 13
-
RO
RO
STATUS
048
4E3AH
setpoint
Current Setpoint
0,0 to 60,0
1/10°C
RW/d
RO
STATUS
049
RESET
User Adjust Temperature
-5,0 to 5,0
1/10 K
RO
RO/F
STATUS
050
IAT_OFF
IAT Offset
-4,0 to 4,0
1/10 K
RO
RO/F
STATUS
Содержание Ereba He Series
Страница 1: ...Instruction manual 05 2019 10195 Inverter Reversible Air to Water Heat Pumps EREBA He...
Страница 94: ......
Страница 95: ......