(Fig. 74)
If no synchronizer is detected by the host, the above menu is displayed. Please turn off the power of the machine,
check whether the synchronizer cable is damaged, whether the connectors are tight, whether the synchronizer cable
tightly contacts with the socket of the host. Then turn on the power of the machine to observe again. If there is no
improvement, contact the manufacturer.
(Fig. 75)
As shown in the above alarm menu, it prompts "Group PA (FUSE = F1)", indicating that the fuse F1 of the power
supply board is broken. If it prompts "Group PB (FUSE = F2)", indicating that the fuse F2 of the power supply
board is broken.
In the above circumstance, turn off the machine's power supply, check whether the fuse F1 or F2 is burnt or bad, and
replace it with good one (250V/5A).If the fuse is burnt, probably the actuator wire is damaged or actuator overload,
please carefully check and repair, before turning on the power again.
14. Special functions
Encoder error
Encoder connection error
Repair and turn on the power again
Group PA (FUSE=F1)
Repair and turn on the power again