- 25 -
© 2021 Chromalox
®
, Inc.
1-888-996-9258
Model
SCR Power Pack
Mmax2
3 Phase SCR Power Controller complete with Lugs and I2T Fusing
1, 2
Code Control Configuration
5
Proportional Control, DOT Zero-Crossover Firing, Command Input Signals: 4-20mA, 0-5
VDC, 1-5 VDC (via Modbus RTU/485 only), 0-10 VDC, Remote 0-1000 OHM Potentiometer
w/Manual Override, Modbus RTU/RS485 Communications. RTD Heat Sink Temperature
Sensor with Two Set-Points, Automatic Line Sensing 50/60HZ, Remote Permissive Stop
Input, Form “C” Dry Contact Alarm Output, Staged Heating w/Digital Calibration Zero /
Span Adjustments(4-8 mA, 8-12 mA,12-16 mA,16-20 mA (via Modbus RTU/RS485 only),
LED Diagnostics: Command Input, Main/Trigger Boards Running, SCR Status per Phase,
Diagnostic Kit via Modbus RTU/RS485: Highest Heat Sink Temperature, Last Heat Sink
Temperature, Highest and Lowest Ambient Temperature, Line Frequency Monitoring,
Third Party Certifications: UL, cUL, CE, DEMKO (650 A and below).
Code Current at 50˚C (104˚F) Ambient
01
30 Amp
02
50 Amp
03
75 Amp
Code Line Voltage
1
120 - 480 Vac
2
575 Vac
Code Instrument Power
1
120 to 240Vac 50/60Hz
Code Remote Manual A`djust/Auto Manual Switch
3
0
None
1
Pot with 0-100% dial and local/Remote Switch,
Single Turn 1K ohm Potentiometer
(Requires Proportional Board)
Mmax2 -
5
01
1
1
0
Typical Model Number
1) SCR fusing is for semiconductor protection only, not wire protection.
2) Supplied loose for customer mounting. 575V fusing only
3) Supplied loose for customer mounting.
Note:
Storage Temperature 14ºF to 158ºF (-10ºC to 70ºC).
CE Application requires filters.
Chromalox Part Numbers
0005-60056 — Line filter, three phase, 440VAC
0005-60057 — Line filter, 120-230VAC
CE application requires filter.
MiniMax 2 Ordering Information