Maintenance

Connections – Loose connections in the power wiring will generate hot spots. These will cause degradation 
of electronic equipment. Periodic inspections should be made to ensure that connections are secure and 
that there are no signs of excessive heating such as discoloration, and so on.

Corrosion – If the power module is installed in an environment with high humidity or dampness, electrical 
connections may suffer corrosion. Periodically check the power module for corrosion.

Damage – Periodically check for rodent damage to wiring and other components.

Filters – Many high-powered control enclosures rely on blowers or fans to maintain a safe operating temper-
ature. The filters used with these devices should be changed on a periodic basis to insure adequate enclo-
sure cooling is maintained.

Dust – Periodically check for dust or other particulate buildup on heatsinks and bus bars.

READ AND UNDERSTAND BEFORE 

CARRYING OUT THE WORK DETAILED BELOW

WARNING

HAZARDOUS VOLTAGE: Disconnect all power before perform-

ing any maintenance or examining the power module. Ex-

posed terminals may carry LETHALLY HIGH VOLTAGES when 

power is applied.

Содержание MiniMax 1

Страница 1: ...PK565 User s Manual P N 0037 75589 www chromalox com 800 443 2640 2021 Chromalox Inc MiniMax Digital ...

Страница 2: ......

Страница 3: ...1 2 and 3 include Zero Crossover Firing Isolated Control Circuit On Off Control Inputs 120 thru 240 Vac 5 32 Vdc Dry Contact Closure Proportional DOT Firing Inputs 4 20 mA 0 5 Vdc 1 5 Vdc 0 10 Vdc Remote Manual Adjust Optional Remote Auto Manual Switch Optional Electronically Protected with Temperature Warning and Stop System Cycle Resolution 3 5 7 11 13 17 19 Shorted SCR Detection Optional Soft S...

Страница 4: ...4 3 Before You Install 5 4 Installation 6 4 1 Mounting 6 4 2 Wiring 8 4 2 1 Power Load Wiring 8 4 2 2 Instrument Power 11 4 2 3 Grounding 11 4 2 4 Command Signal Wiring 11 4 2 5 Calibration 17 5 Specifications 18 6 Maintenance 19 7 Troubleshooting 20 8 Parts and Accessories 21 9 Warranty and Return Information 22 ...

Страница 5: ... you do not follow instructions Damage Prevention Messages You will see other IMPORTANT messages that are proceeded by the word CAUTION that are intended to help prevent damage to the MiniMax or other equipment Note that Damage Prevention Messages are NOT accompanied by the Safety Alert Symbol Key Safety Practices All personnel working on high voltage electrical equipment must adhere to all nation...

Страница 6: ...hermal shock The power SCR assemblies consist of one two or three pairs of SCRs connected back to back with an op tional semiconductor fuse RC Snubber and MOV protection The firing circuit is based on a common On Off control board with plug and play Shorted SCR and DOT fired plug in boards Diagnostic indicators are included Plug in terminal blocks for easy customer interface are also provided Mini...

Страница 7: ...Before choosing a location in which to mount your MaxPac please consider the following Temperature When mounting the SCR unit in a control panel attention should be paid to the enclosure temperature The SCR is rated to perform at its nameplate current rating in temperatures up to 50 C 122 F Ensure that adequate ventilation is provided or some other method of maintaining the correct cabinet tempera...

Страница 8: ... environment for the unit s operation The space required for mounting the MiniMax Power Pak depends upon the model The table below refers to the figures on the following pages These figures illustrate the dimensions and mounting holes for the vari ous MiniMax Power Pak models Please refer to these figures before mounting your unit Figure Model 1 MiniMax 1 30 50 Amp Mounting Base 1 MiniMax 1P 30 50...

Страница 9: ...9 05MM 3 25 82 55MM 4 00 101 60MM ø 28 ø7 14MM 4 PLACES MINIMAX 2 30 50 AMP MOUNTING BASE GND 8 5 215 90MM 9 50 241 30MM 0 00 0 00MM 0 75 19 05MM 3 25 82 55MM 4 00 101 60MM ø 28 ø7 14MM 4 PLACES MINIMAX 2 75 AMP MOUNTING BASE GND 13 00 330 20MM 14 00 355 60MM 0 00 0 00MM 0 75 19 05MM 3 25 82 55MM 5 00 127 00MM ø 28 ø7 14MM 4 PLACES 13 00 330 20MM 14 00 335 60MM 0 00 0 00MM 0 75 19 05MM 3 25 82 55M...

Страница 10: ... form electrical wiring for the MiniMax Power Paks LETHALLY HIGH VOLTAGES are associated with this equipment and are dangerous if improperly installed WARNING The following wiring instructions are for the Digital Minimax only If using Analog Minimax contact factory for appropriate wiring schematics Analog Minimax is designated as MMAXI II or III followed by the number 1 2 3 or 4 under the firing m...

Страница 11: ...L2 X1 X3 L2 Connection is NOT on MiniMax Four Wire 3 Leg Control MINIMAX 3 L1 L2 L3 X1 X2 X3 N N Connection is NOT on MiniMax IMPORTANT The I2 t fuses installed on the SCR are designed to protect the SCR from faults on the load connection side They are NOT intended to provide wire protection CAUTION ...

Страница 12: ...n the SCR are designed to protect the SCR from faults on the load connection side They are NOT intended to provide wire protection CAUTION Three Wire 3 Leg Control MINIMAX 3 L1 L2 L3 X1 X2 X3 Single Phase transformer Coupled MINIMAX 1P L2 L2 L1 X1 L2 connection to MiniMax is instrument power only ...

Страница 13: ...Customer Connection Please refer to the figures on page 12 for illustrations of the 6 8 and 10 pin input terminals 4 2 2 Instrument Power MiniMax requires 120 or 230 Vac 50 60Hz for instrument power This voltage supplies power for the control circuits fans high temperature warning indicator and shorted SCR Indicators see Fig 1 on page 15 This supply is fused on the main circuit board 4 2 3 Groundi...

Страница 14: ...OSED SWNC CONTACT NORMALLY OPEN SWNO SWITCH ASSEMBLY SW PANEL TO BE MOUNTED TO LEGEND PLATE LP AUTO HAND SWITCH KNOB SW AUTO HAND WIRING 1 4 NC NO 1K POTENTIOMETER J2 CW MiniMax 1 2 and 3 On Off Control Signals AC Input The 120 thru 230 Vac signal lines are connected to terminal J1 7 8 see Fig 9 on page 21 An input voltage of 120 to 230 Vac turns the power On The turn OFF voltage is 0 Vac DC Input...

Страница 15: ...n off input is isolated by an opto coupler The dc and contact closure inputs are buffered by the circuitry The drive signal to the SCR trigger boards The temperature alarm The heat sink temperature is derived from a resistive temperature detection RTD mounted on the heat sink This is then compared to two set points The first alarm is a warning and activates the externally connected device This all...

Страница 16: ...set rotary switch at SW1 to position 0 0 10Vdc Select AUTO mode by jumpering J2 4 J2 5 and then set rotary switch at SW1 to position 2 0 5Vdc Select AUTO mode by jumpering J2 4 J2 5 and then set rotary switch at SW1 to position 3 1 5Vdc Select AUTO mode by jumpering J2 4 J2 5 and then set rotary switch at SW1 to position 4 0 20mA Select AUTO mode by jumpering J2 4 J2 5 and then set rotary switch a...

Страница 17: ...apidly if phase voltage is not present or if SCR is shorted in both directions LD4 Switch SCR2 OFF in normal operation Turns ON if shorted SCR is de tected in one direction Blinks rapidly if phase voltage is not present or if SCR is shorted in both directions LD5 Switch SCR3 OFF in normal operation Turns ON if shorted SCR is de tected in one direction Blinks rapidly if phase voltage is not present...

Страница 18: ...ly applied Also make sure the Emergency Shutdown if used has N O contacts and jumper pins 4 5 on the 10 pin connector if remote manual bias are not used Please read the information on calibration at the end of this section for current limit settings for loads with extreme hot to cold ratios or those that are overrated Other ranges may be field calibrated by use of zero and gain potentiometers IMPO...

Страница 19: ...ositive inputs to the MiniMax Power Pak EXAMPLE 0 5 mA input à set to 0 mA input 4 20 mA input à set to 4 mA input 7 With power off connect line voltage and load as shown 8 Connect meter to input and output WARNING Set meter to correct scale to read proper input or output 9 Apply power to unit 10 Adjust input signal to low end of scale 11 Using the Zero pot adjust the output voltage just to zero v...

Страница 20: ...erature Voltage Output Indicator Output 100 mA Instrument Power Shorted SCR Voltage Output Indicator Output 100 mA Instrument Power MiniMax 1 2 and 3 MiniMax 1P Control Inputs Accepts all of the following as standards Phase Angle Control Signal Input Input Impedance 1 5 0 5 mA 1K Ohms 4 20 0 20 mA 250 Ohms 10 50 0 50 mA 100 Ohms Optional Remote Manual Adjust Fan Power 120 or 230 VAC 50 60 Hz Outpu...

Страница 21: ...heck the power module for corrosion Damage Periodically check for rodent damage to wiring and other components Filters Many high powered control enclosures rely on blowers or fans to maintain a safe operating temper ature The filters used with these devices should be changed on a periodic basis to insure adequate enclo sure cooling is maintained Dust Periodically check for dust or other particulat...

Страница 22: ... damage on the trigger board Observation Possible Root Cause LD3 SCR1 light is ON and Alarm relay engaged Shorted SCR1 LD4 SCR2 light is ON and Alarm relay engaged Shorted SCR2 LD5 SCR3 light is ON and Alarm relay engaged Shorted SCR3 LD3 SCR1 light is blinking and Alarm relay engaged Missing phase or phase error SCR1 LD4 SCR2 light is blinking and Alarm relay engaged Missing phase or phase error ...

Страница 23: ...m 26 inch lb 3Nm SCR Replacement 575 Vac Be sure to replace thermstrate interface material and torque as follows MFG Part SCR Part Thermstrate Part Torque inch lb Torque inch lb to Heat Sink to Terminals SKKT42 14E 0002 42519 0029 00700 44 inch lb 5 Nm 26 inch lb 3Nm SKKT92 14E 0002 47561 0029 00700 44 inch lb 5 Nm 26 inch lb 3Nm MiniMax 1 2 and 3 Accessories Part Number Description 0135 20117 Pot...

Страница 24: ...instructions Users are responsi ble for the suitability of the products to their application There is no warranty against damage resulting from corrosion misapplication improper specification or other operating conditions beyond our control Claims against the carrier company for damage in transit must be filed by the buyer Returns Items returned to Chromalox Instruments and Controls must be accomp...

Страница 25: ...e Diagnostic Kit via Modbus RTU RS485 Highest Heat Sink Temperature Last Heat Sink Temperature Highest and Lowest Ambient Temperature Line Frequency Monitoring Third Party Certifications UL cUL CE DEMKO 650 A and below Code Current at 50 C 104 F Ambient 01 30 Amp 02 50 Amp 03 75 Amp Code Line Voltage 1 120 480Vac 2 575Vac Code Instrument Power 1 120 to 240Vac 50 60Hz Code Remote Manual Adjust Auto...

Страница 26: ...ge 1 120 Vac 2 208 Vac 3 240 Vac 4 277 Vac 5 480 Vac 6 575 Vac Code Remote Manual Adjust Auto Manual Switch3 0 None 1 Pot with 0 100 dial and local Remote Switch Single Turn 1K ohm Potentiometer Requires Proportional Board Mmax 1P 2 01 1 1 Typical Model Number 1 SCR fusing is for semiconductor protection only not wire protection 2 Supplied loose for customer mounting 575V fusing only 3 Supplied lo...

Страница 27: ...ghest Heat Sink Temperature Last Heat Sink Temperature Highest and Lowest Ambient Temperature Line Frequency Monitoring Third Party Certifications UL cUL CE DEMKO 650 A and below Code Current at 50 C 104 F Ambient 01 30 Amp 02 50 Amp 03 75 Amp Code Line Voltage 1 120 480 Vac 2 575 Vac Code Instrument Power 1 120 to 240Vac 50 60Hz Code Remote Manual A djust Auto Manual Switch3 0 None 1 Pot with 0 1...

Страница 28: ...ture Line Frequency Monitoring Third Party Certifications UL cUL CE DEMKO 650 A and below Code Current at 50 C 104 F Ambient 01 30 Amp 02 50 Amp 03 75 Amp Code Line Voltage 1 120 480 Vac 2 575 Vac Code Instrument Power 1 120 to 240 Vac 50 60Hz Code Remote Manual Adjust Auto Manual Switch 0 None 1 Pot with 0 100 dial and local Remote Switch Single Turn 1K ohm Potentiometers Requires Pro portional B...

Отзывы: