Appendix C
CMX-250, Heat Only 4081 Controller
Configuration Menu
Lock Code
10
Input Configuration
Input 1 setup
Input Type
J Thermocouple
Engineering Units
˚F
Decimal Point Position
1234
Scaled Input Lower Limit
32˚F
Scaled Input Upper Limit
260 °F
Cold Junction Compensation
Enabled
Input Filter Time
2.0 sec
Control Configuration
Control Select
Control Standard
Control Enable/Disable
Control Enabled
Select Auto/Manual Control
Automatic Control
Control Type
SINGLE
Primary Control Action
Reverse
PID set Use
PID set 1
Set 1 Primary Pb
15°F
Set 1 Secondary Pb
10˚F
Set 11ntegral
0.01 s
Set 1 Derivative
20.0s
Set 1 overlap/deadband
5˚F
Manual Reset
0%
Anti windup limit
100
Primary Cycle Time
30.0 s
Secondary Cycle Time
10.0 s
Primary Power Lower Limi
0.00%
Primary Power Upper Limit
100.00%
Secondary Power Lower Limit
0.00%
Secondary Power Upper Limit
100.00%
Sensor Break
Off
Set Point Lower Limit
32˚F
Set Point Upper Limit
250˚F
Set Point Ramp Rate
Off
Main setpoint source
Local Set point
Alternate Set Point Source
Not Used
Main Set Point
250°F
Output Configuration
Output 1 Usage
Unused
Output 2 Usage
Primary
Output 3 Usage
OR alarm-events reverse
OPR3 OR selection
Alarms 1v
Output 3 Latch enable
Enabled
Output 4 Usage
UNUSED
Alarm Configuration
Alarm 1
Alarm 1 Type
Process High
Alarm 1 source
universal input 1
Process High Alarm Value
260˚F
Process High Alarm Hysteresis
1˚F
Minimum Duration
15 sec
Power-Up Inhibit Alarm 1
Uninhibited
Communication Configuration
Modbus RTU Parity
None
Modbus RTU Data Rate
19200
Serial Communication
Enabled